Product Family | I/O Systems: Active - Standalone |
---|
Product Sub Family | LioN-R |
---|
Item Description | 0980 ESL 813-EIP 8DI/8DO-M12-R |
---|
Device Type | I/O Module |
---|
Protocol | EtherNet/IP |
---|
I/O Function | 8DI 8DO |
---|
Bus Connection | M12, 4-poles, D-coded |
---|
Power Connection (System Supply) | 7/8" Power, 4-poles |
---|
I/O Connection | M12, 5-poles, A-coded |
---|
I/O Type | Digital Input and Digital Output |
---|
General Data
Housing Material | Metal, Zinc Die-cast |
---|
Housing Plating | Nickel, matt |
---|
Housing Color | Grey Metallic |
---|
Protection Degree / IP Rating** | IP65, IP67 |
---|
Potted | Yes |
---|
Dimensions (W x H x D) | 60 mm x 31 mm x 265 mm |
---|
Weight | 630 g |
---|
Ambient Temperature (Operation)* | -10 °C to 60 °C |
---|
Pollution Degree | 3 acc. to EN 60664-1, VDE 0110-1 |
---|
Vibration Resistance | 15 g / 5 -500 Hz |
---|
Shock Resistance | 50 g / 11ms |
---|
Contact Base Material | M12, D-coded, CuSn, Gold-plated | 7/8" CuZn, Gold-plated |
---|
Contact Bearer Material | PA / TPU |
---|
O-Ring Material | FKM |
---|
Mounting | 2 hole screw mounting. Use standard M6 x 25 / 30 screws with toothed lock washer (as per DIN 125) and self-locking nuts. |
---|
Fastening Torque (Fixing Screw) | M6: 1 Nm |
---|
Fastening Torque (Ground Connection (FE)) | M4: 1 Nm |
---|
Fastening Torque (Bus Connection) | M12: 0.5 Nm |
---|
Fastening Torque (Power Connection) | 7/8": 1.5 Nm |
---|
Fastening Torque (I/O Connection) | M12: 0.5 Nm |
---|
Included in Delivery | Attachable Labels: 15x, Sealing Caps: 4x M12 |
---|
EtherNet/IP
Protocol (EtherNet/IP) | EtherNet/IP |
---|
Connection | M12 LAN, 4-poles, D-coded |
---|
Number of Connections | 2 |
---|
Specification | CIP Edition 3.9 / EIP Adaption of CIP 1.1x |
---|
Transmission Rate | Fast Ethernet (10/100 Mbit/s), Full Duplex |
---|
Transmission Method | 100 BASE-TX, with auto negotiation and auto crossing |
---|
Cycle Time / Requested Packet Interval (RPI) | min. 1 ms |
---|
Addressing | BootP, DHCP, Rotary Address Switches |
---|
Address Switches Range | 0 to 255 dec |
---|
Connection Types | Exclusive Owner, Input Only, Listen Only |
---|
Quick Connect (QC) | Supported, ≤ 500 ms |
---|
Device Level Ring (DLR) | Supported, beacon based |
---|
Supported Network Protocols (Other) | ACD, ARP, BootP, DHCP, HTTP, IGMP, Ping, TCP/IP |
---|
Power Supply
Connection Module Supply Voltage | 7/8" Power, 4-poles |
---|
Number of Connections | 2 |
---|
Current Carrying Capacity of Connector | max. 9 A |
---|
Module Supply Voltage (Nominal) | 24 V DC (SELV/PELV) |
---|
Module Supply Voltage (Range) | 18 V DC to 30 V DC |
---|
Current Consumption (typ.) | 100 mA (at 24 V DC) |
---|
Reverse Polarity Protection | Yes |
---|
Status Indicator (System Supply) | LED green |
---|
Diagnostic Indicator | LED red |
---|
Connection Sensor Supply Voltage | via Module Supply Connection |
---|
Current Carrying Capacity of Connector | max. 9 A |
---|
Sensor Supply Voltage (Nominal) | 24 V DC (SELV/PELV) |
---|
Sensor Supply Voltage (Range) | 18 V DC to 30 V DC |
---|
Reverse Polarity Protection | Yes |
---|
Status Indicator (Sensor Supply) | LED green |
---|
Diagnostic Indicator | LED red |
---|
Connection Actuator Supply Voltage | via Module Supply Connection |
---|
Current Carrying Capacity of Connector | max. 9 A |
---|
Actuator Supply Voltage (Nominal) | 24 V DC (SELV/PELV) |
---|
Actuator Supply Voltage (Range) | 18 V DC to 30 V DC |
---|
Reverse Polarity Protection | Yes |
---|
Status Indicator (Actuator Supply) | LED green |
---|
Diagnostic Indicator | LED red |
---|
Digital Input Channels
Number of Digital Input Channels | max. 8, fixed |
---|
Connection | M12, 5-poles, A-coded |
---|
Number of Ports | 4x, X1 to X4 |
---|
Channel Type | Type 3 acc. to IEC 61131-2 |
---|
Sensor Current Supply | max. 200 mA per port (at 30°C) |
---|
Input Wiring | 2-, 3-, 4-wire |
---|
Nominal Voltage | 24 V DC via US (module power supply) |
---|
Nominal Current | typ. 5 mA |
---|
Sensor Type | PNP |
---|
Input Voltage Range "0" signal | -3 V DC …+5 V DC |
---|
Input Voltage Range "1" signal | 11 V DC … 30 V DC |
---|
Input Filter Time | 3 ms, fixed |
---|
Protective Circuit | Electronicaly: Overload protection, short-circuit protection |
---|
Status Indicator (Inputs) | LED white or yellow per channel |
---|
Diagnostic Indicator | LED red per port |
---|
Digital Output Channels
Number of Digital Output Channels | max. 8, fixed |
---|
Connection | M12, 5-poles, A-coded |
---|
Number of Ports | 4x, X5 to X8 |
---|
Channel Type | p-switching |
---|
Output Current per Channel | max. 1.6 A |
---|
Output Wiring | 2-, 3-wire |
---|
Nominal Voltage | 24 V DC via UL (actuator power supply) |
---|
Output Current per Module | max. 9 A |
---|
Galvanically Isolated | Yes |
---|
Protective Circuit | Electronicaly: Overload protection, short-circuit protection |
---|
Overload Behavior | Manual restart |
---|
Status Indicator (Outputs) | LED white or yellow per channel |
---|
Diagnostic Idicator | LED red per channel |
---|
Electrical Isolation
US (System Supply Voltage) / FE | 500 V DC |
---|
US / UL (Actuator Supply Voltage) | 500 V DC |
---|
UL / FE | 500 V DC |
---|
Bus connection / FE | 2000 V DC |
---|
EMC Conformance
EMC Directive | 2014/30/EU |
---|
EN 61000-4-2 Electrostatic Discharge (ESD) | Criterion B; 4 kV contact discharge, 8 kV air discharge |
---|
EN 61000-4-3 Electromagnetic Field | Criterion A; Field intensity: 10 V/m |
---|
EN 61000-4-4 Fast Transients (Burst) | Criterion B, 2 kV |
---|
EN 61000-4-5 Surge Voltage | Criterion B; DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical); For I/O ports with cables ≤ 30m |
---|
EN 61000-4-6 Conducted immunity | Criterion A; Test voltage 10 V |
---|
EN 55022 Radio Interference Properties | Class A |
---|
Safety & Environmental Compliance
CE | Yes |
---|
RoHS Compliant | Yes |
---|
China RoHS-Compliant | Yes |
---|
Approvals
UL | cULus Listed, UL 508 |
---|
UL-File | E230848 |
---|
CSA | Yes, via UL |
---|
ODVA | Yes |
---|
Notes
Protection Degree / IP Rating Note | ** only if mounted and locked in combination with Hirschmann / Lumberg Automation connector. |
---|
System Power Supply Connection Note | *do not connect / disconnect under voltage! |
---|
Update and Revision | Revision Number: 0.53 Revision Date: 05-24-2023 |
---|