DNV GL, Shipboard, Category 6A Enhanced Premise Horizontal Cable (625MHz), 4-Pair, 23 AWG Solid Bare Copper conductors, U/FTP, Foam Polyethylene insulation, each pair with Beldfoil® shield, AWG 26 solid tinned copper drainwire, LSZH jacket, CPR Euroclass Eca
Specifications
Specifications
Product Overview
| Suitable Applications | Horizontal and building backbone cable; Support current and future Category 6A and 6 applications, such as: 10GBase-T (10 Gigabit Ethernet), 1000Base-T (Gigabit Ethernet), 100 Base-T, 10 Base-T, FDDI, ATM | 
|---|
| Patent | This product has one or more applicable patents. More information on patents can be found at https://www.belden.com/patents. | 
|---|
Construction Details
Conductor
| Element | Size | Stranding | Material | Number of Pairs | Number of Element | 
|---|
| Individual Shielded Pair | 23 AWG | Solid | BC - Bare Copper | 4 | 8 | 
Insulation
| Element | Material | Nom. Insulation Diameter | Color Code | 
|---|
| Individual Shielded Pair | PE - Polyethylene (Foam) | 1.32 mm (0.0520 in) | White / Blue, White / Orange, White / Green, White / Brown | 
Cable Core
| Description | 
|---|
| 2 twisted insulated conductors with overall foil, 4 pairs all twisted together with AWG 26 tinned copper drain wire | 
Inner Shield
| Element | Shield Type | Material | Coverage | 
|---|
| Individual Shielded Pair | Tape | Bi-Laminate (Alum+Poly) | 100% | 
| Table Notes | Aluminum facing outside | 
|---|
Outer Shield
| Shield Type | Material | Drainwire Type | 
|---|
| Tape | Bi-Laminate (Alum+Poly) | 26 AWG (Solid) TC | 
| Table Notes | Aluminium facing outside | 
|---|
Outer Jacket
| Material | Nom. Diameter | Ripcord | 
|---|
| LSZH - Low Smoke Zero Halogen (Flame Retardant) | 7.5 mm (0.30 in) | Yes | 
| Overall Cable Diameter (Nominal) | 7.5 mm (0.30 in) | 
|---|
Electrical Characteristics
Electricals
| Max. Conductor DCR | Max. Mutual Capacitance | Max. Capacitance Unbalance | Nom. Characteristic Impedance | 
|---|
| 95 Ohm/km | 56 pF/m (17 pF/ft) | 160 pF/100m | 100 Ohm | 
Delay
| Max. Delay Skew | Nom. Velocity of Prop. | 
|---|
| 45 ns/100m | 77% | 
High Frequency
| Frequency [MHz] | Max. Insertion Loss (Attenuation) | Min. NEXT [dB] | Min. PSNEXT [dB] | Min. ACR [dB] | Min. PSACR [dB] | Min. ACRF (ELFEXT) [dB] | Min. PSACRF (PSELFEXT) [dB] | Min. RL (Return Loss) [dB] | Min. PSANEXT [dB] | Min. PSAACRF [dB] | Min. TCL [dB] | Min. ELTCTL [dB] | 
|---|
| 1 | 2.1 dB/100m | 75.3 | 72.3 | 73.2 | 70.2 | 68 | 65 | 20 | 67 | 67 | 40 | 35 | 
| 4 | 3.8 dB/100m | 66.3 | 63.3 | 62.5 | 59.5 | 56 | 53 | 23 | 67 | 66.2 | 34 | 23 | 
| 10 | 5.9 dB/100m | 60.3 | 57.3 | 54.4 | 51.4 | 48 | 45 | 25 | 67 | 58.2 | 30 | 15 | 
| 16 | 7.5 dB/100m | 57.2 | 54.2 | 49.8 | 46.8 | 43.9 | 40.9 | 25 | 67 | 54.1 | 28 | 10.9 | 
| 31.2 | 10.5 dB/100m | 52.9 | 49.9 | 42.4 | 39.4 | 38.1 | 35.1 | 23.6 | 67 | 48.3 | 25.1 | 5.1 | 
| 62.5 | 15 dB/100m | 48.4 | 45.4 | 33.4 | 30.4 | 32.1 | 29.1 | 21.5 | 65.6 | 42.3 | 22 |  | 
| 100 | 19.1 dB/100m | 45.3 | 42.3 | 26.2 | 23.2 | 28 | 25 | 20.1 | 62.5 | 38.2 | 20 |  | 
| 125 | 21.5 dB/100m | 43.8 | 40.8 | 22.3 | 19.3 | 26.1 | 23.1 | 19.4 | 61 | 36.3 | 19 |  | 
| 200 | 27.6 dB/100m | 40.8 | 37.8 | 13.2 | 10.2 | 22 | 19 | 18 | 58 | 32.2 | 17 |  | 
| 250 | 31.1 dB/100m | 39.3 | 36.3 | 8.3 | 5.3 | 20 | 17 | 17.3 | 56.5 | 30.2 | 16 |  | 
| 300 | 34.3 dB/100m | 38.1 | 35.1 | 3.9 | 0.9 | 18.5 | 15.5 | 17.3 | 55.3 | 28.7 |  |  | 
| 500 | 45.3 dB/100m | 34.8 | 31.8 | -10.4 | -13.4 | 14 | 11 | 17.3 | 52 | 24.2 |  |  | 
| 625 | 51.2 dB/100m | 33.4 | 30.4 | -17.8 | -20.8 | 12.1 | 9.1 | 17.3 | 50.6 | 22.3 |  |  | 
| Table Notes | Limits below 4 MHz and at 625 MHz are for information only.
Reference standard: IEC 61156-5 | 
|---|
Transfer Impedance
| Frequency | Max. Transfer Impedance | 
|---|
| 1 Mhz | Max. 50 mOhm/m | 
| 10 Mhz | Max. 100 mOhm/m | 
| 30 Mhz | Max. 200 mOhm/m | 
| 100 Mhz | Max. 1000 mOhm/m | 
| Transfer Impedance Class | Grade 2 | 
|---|
| Screening Class | Type Ib | 
|---|
| Table Notes | Coupling Attenuation | 
|---|
Voltage
Mechanical Characteristics
Temperature
| Operating | Installation | 
|---|
| -30°C to +60°C | 0°C To +50°C | 
Bend Radius
| Stationary Min. | Installation Min. | 
|---|
| 33 mm (1.3 in) | 66 mm | 
| Max. Pull Tension | 79 N (18 lbf) | 
|---|
| Bulk Cable Weight | 44 kg/km | 
|---|
Standards and Compliance
| Environmental Suitability | Indoor - Euroclass Eca | 
|---|
| Flammability / Reaction to Fire | IEC 60332-1-2, IEC 60332-3-22 | 
|---|
| CPR Compliance | CPR Euroclass: Eca | 
|---|
| IEEE Compliance | PoE: IEEE 802.3bt Type 1, Type 2, Type 3, Type 4 | 
|---|
| Data Category | Category 6A | 
|---|
| TIA/EIA Compliance | ANSI/TIA 568.2-D | 
|---|
| Third Party Performance Verification | DNV GL certification | 
|---|
| ISO/IEC Compliance | ISO/IEC 11801-1, IEC 61034-2 - Smoke Density Min Transmittance = 60% | 
|---|
| CENELEC Compliance | EN 50173-1, Segregation class according EN50174-2 = d | 
|---|
| European Halogen Free Standards | IEC 62821-1 Halogen Free Compliance = Yes, IEC 60754-1 - Halogen Amount = Zero, IEC 60754-2 - Halogen Acid Gas Amount - Max. Conductivity = 2.5 µS/mm, IEC 60754-2 - Halogen Acid Gas Amount - Min. pH = 4.3 | 
|---|
| European Directive Compliance | EU CE Mark | 
|---|
| UK Regulation Compliance | UKCA Mark | 
|---|
Product Notes
| Notes | Electrical values are expected performance based on cable testing and representative performance within a typical Belden system. | 
|---|
History
| Update and Revision | Revision Number: 0.100    Revision Date: 03-08-2023 | 
|---|
Documentation
Product Bulletins
Catalogs
Termination Tools
Compliance Documentation
Data Sheets