Description

10GXW Category 6A Enhanced Premise Horizontal Cable (500MHz), 4 Pair, 23 AWG Solid Bare Copper Conductors, F/UTP - Foil Shielded, Riser-CMR, PVC Jacket

Specifications

Specifications

Product Overview

Suitable ApplicationsPremise Horizontal Cable, Ethernet up to 10GBASE-T, Wi-Fi 6, Wi-Fi 5, Surveillance, HDBaseT, PoE++, PoE+, PoE, Noisy Environments
PatentThis product has one or more applicable patents. More information on patents can be found at https://www.belden.com/patents.

Construction Details

Conductor

SizeStrandingMaterialNumber of Pairs
23 AWGSolidBC - Bare Copper4

Insulation

MaterialColor Code
PO - PolyolefinWhite & Blue, White & Orange, White & Green, White & Brown

Outer Shield

Shield TypeMaterialCoverage
TapeBi-Laminate (Alum+Poly)100%

Outer Jacket

MaterialNom. Diameter
PVC - Polyvinyl Chloride0.265 in (6.73 mm)

Electrical Characteristics

Electricals

Max. Conductor DCRMax. Capacitance Unbalance
82 Ohm/km (25 Ohm/1000ft)45 pF/100m

Delay

Max. DelayNom. Velocity of Prop.
537.6 ns/100m70%

Voltage

UL Voltage Rating
300 V (CMR), 300 V (CL3R)

Mechanical Characteristics

Temperature

UL TemperatureOperatingStorage
90°C-20°C To +75°C-20°C To +75°C

Bend Radius

Installation Min.
2.65 in (67.3 mm)
Max. Pull Tension25 lbs (11 kg)
Bulk Cable Weight37 lbs/1000 ft

Standards and Compliance

Environmental SuitabilityRiser, Indoor
Flammability / Reaction to FireUL 1666 Riser, FT4
CEC / C(UL) ComplianceCMR
ICEA ComplianceS-116-732
IEEE ComplianceIEEE 802.3bt Type 1, Type 2, Type 3, Type 4
NEMA ComplianceANSI/NEMA WC-66
Data CategoryCategory 6A
TIA/EIA ComplianceANSI/TIA-568.2-D Category 6A
ISO/IEC ComplianceISO/IEC 11801-1, IEC 61156-5
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), REACH, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)

Product Notes

NotesElectrical values are expected performance based on cable testing and representative performance within a typical system.

History

Update and RevisionRevision Number: 0.6 Revision Date: 04-08-2022
View AllClose