Belden 300% Ground Flexible VFD, 3 Conductor 4AWG (7x19x25) Tinned Copper, XLPE Insulation M4 Color Code+PVC Insulated Ground, Overall Beldfoil®+Tinned Copper Braid(85%) Shield w/4-10AWG Tinned Copper Drains, PVC Inner Jacket, Aluminum Interlock Armor, Black PVC Outer Jacket, 600V MC 90C Dry/Wet SUN RES DIR BUR CT USE Oil Resistant
Specifications
Specifications
Product Overview
Suitable Applications | Variable Frequency Drives (VFD); AC Motor and Drive Systems; Exposure to rodents, crush or impact forces |
---|
Construction Details
Conductor
Element | Number of Element | Size | Stranding | Material |
---|
Conductor(s) | 3 | 4 AWG | 7x19x25 | TC - Tinned Copper |
Ground | 1 | 4 AWG | 7x19x25 | TC - Tinned Copper |
Insulation
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|
Conductor(s) | XLPE - Cross-Linked Polyethylene (Thermoset) | 0.062 in (1.6 mm) | 0.367 in (9.32 mm) | Black and Numbered |
Ground | PVC - Polyvinyl Chloride | 0.062 in (1.6 mm) | 0.367 in (9.32 mm) | Green/Yellow Stripe |
Outer Shield
Shield Type | Material | Coverage |
---|
Tape | Tri-Laminate (Alum+Poly+Alum) | 100% |
Braid | Tinned Copper (TC) | 85% |
Inner Jacket
Material | Nom. Thickness | Nom. Diameter |
---|
PVC - Polyvinyl Chloride | 0.093 in (2.4 mm) | 1.113 in (28.27 mm) |
Armor
Armor Type & Material |
---|
AIA - Aluminum Interlock Armor |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter | Ripcord |
---|
PVC - Polyvinyl Chloride | 0.055 in (1.4 mm) | 1.510 in (38.35 mm) | Yes |
Overall Cable Diameter (Nominal) | 1.510 in (38.35 mm) |
---|
Electrical Characteristics
Electricals
Element | Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Nom. Capacitance Cond-to-Other (Conds + Shield) | Nom. Characteristic Impedence | Nom. Velocity of Prop. | Max. Current |
---|
Conductor(s) | 0.239 Ohm/1000ft (0.784 Ohm/km) | 44 pF/ft (140 pF/m) | 79 pF/ft (260 pF/m) | 42 Ohm | 55% | 95 Amps per Conductor at 30ºC |
Voltage
UL Voltage Rating |
---|
600 V (MC) |
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|
90°C Dry, 90°C Wet | -25°C To +90°C |
Bend Radius
Stationary Min. | Installation Min. |
---|
13.9 in (353 mm) | 13.9 in (353 mm) |
Max. Pull Tension | 2156 lbs (977.9 kg) |
---|
Bulk Cable Weight | 1461 lbs/1000ft (2174 kg/km) |
---|
Standards and Compliance
Environmental Suitability | Indoor, Outdoor, Sunlight Resistance, Oil Resistance, Burial |
---|
Sustainability | CA Prop 65 |
---|
Flammability / Reaction to Fire | UL 1685 Vertical Tray, 1202, 383 Vertical Tray Flame Test (70,000 BTU) |
---|
NEC / UL Compliance | Article 336, MC |
---|
European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
---|
APAC Compliance | China RoHS II (GB/T 26572-2011) |
---|
History
Update and Revision | Revision Number: 0.73 Revision Date: 12-20-2022 |
---|
Documentation
Catalogs
Technical Resources
Videos
Compliance Documentation
Data Sheets