Belden

1229532 - VFD 100% Gnd, 3C #4/0 Str TC XLPE Ins + #4/0 Symm. Seg. Gnd (3 of #2) Str BC, CTS, PVC Jkt, AIA Armor, Blk PVC Jkt, 600V MC 90C Dry/Wet

(No reviews yet) Write a Review
SKU:
1229532
Shipping:
Calculated at Checkout
$0.00

Description

Belden 100% Ground Flexible VFD, 3 Conductor 4/0AWG (7x19x18) Tinned Copper XLPE Insulation M4 Color Code + 4/0AWG Symmetrical Segmented Ground (3 of 2AWG) Bare Copper Stranded, Overall Dual Copper Tapes Helically Applied Shield, PVC Inner Jacket, Aluminum Interlock Armor, Black PVC Outer Jacket, 600V MC 90C Dry/Wet SUN RES DIR BUR CT USE Oil Resistant

Specifications

Specifications

Put-Up TypeReel

Product Overview

Suitable ApplicationsVariable Frequency Drives (VFD); AC Motor and Drive Systems; Exposure to rodents, crush or impact forces

Construction Details

Conductor

ElementNumber of ElementSizeStrandingMaterialNotes
Conductor(s)34/0 AWG7x19x18TC - Tinned Copper
Ground32 AWG7x19x23BC - Bare CopperSegmented Grounds

Insulation

ElementMaterialNom. ThicknessNom. Insulation DiameterColor Code
Conductor(s)XLPE - Cross-Linked Polyethylene (Thermoset)0.057 in (1.4 mm)0.684 in (17.4 mm)Black and Numbered
GroundNo Insulation

Outer Shield

Shield TypeMaterialCoverage
Helical TapeBare Copper (BC)100%
Helical TapeBare Copper (BC)100%

Inner Jacket

MaterialNom. ThicknessNom. Diameter
PVC - Polyvinyl Chloride0.083 in (2.1 mm)1.652 in (41.96 mm)

Armor

Armor Type & Material
AIA - Aluminum Interlock Armor

Outer Jacket

MaterialNom. ThicknessNom. DiameterRipcord
PVC - Polyvinyl Chloride0.065 in (1.7 mm)2.079 in (52.81 mm)Yes
Overall Cable Diameter (Nominal)2.079 in (52.81 mm)

Electrical Characteristics

Electricals

ElementNom. Conductor DCRNom. Capacitance Cond-to-CondNom. Capacitance Cond-to-Other (Conds + Shield)Nom. Characteristic ImpedenceNom. Velocity of Prop.Max. Current
Conductor(s)0.047 Ohm/1000ft (0.15 Ohm/km)29 pF/ft (95 pF/m)53 pF/ft (170 pF/m)63 Ohm55%260 Amps per Conductor at 30ºC

Voltage

UL Voltage Rating
600 V (MC)

Mechanical Characteristics

Temperature

UL TemperatureOperating
90°C Dry, 90°C Wet-25°C To +90°C

Bend Radius

Stationary Min.Installation Min.
24.9 in (632 mm)24.9 in (632 mm)
Max. Pull Tension10294 lbs (4669.3 kg)
Bulk Cable Weight3912 lbs/1000ft (5822 kg/km)

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, Oil Resistance, Burial
SustainabilityCA Prop 65
Flammability / Reaction to FireUL 1685 UL Loading, 1202, 383 Vertical Tray Flame Test (70,000 BTU)
NEC / UL ComplianceArticle 336, MC, XHHW-2
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.74 Revision Date: 04-14-2023

Documentation

Catalogs

Technical Resources

Videos

Compliance Documentation

Data Sheets