Belden

123076F - Fieldbus, 1 Pr #18 Str TC, PP ins, OS, PVC Jkt, AIA Armor, PVC Jkt, ISA/SP-50 Type A, PLTC, CM

(No reviews yet) Write a Review
SKU:
123076F
Shipping:
Calculated at Checkout
$0.00

Description

Fieldbus, 1 Pair 18AWG (7x26) Tinned Copper, PP insulation, Overall Beldfoil® Shield, PVC Inner Jacket, Aluminum Interlock Armor, PVC Outer Jacket, ISA/SP-50 Type A, , PLTC, CM

Specifications

Specifications

Product Overview

Suitable Applicationsexposure to rodent, crush, or cut through force, harsh environment digital and serial two-way communication, oil and gas extraction and refining sites, petrochemical, Profibus process automation or Foundation FieldBus process automation, extreme temperature environments, exposure to humidity/moisture, dust, and oil, remote locations long distance applications, etc.

Construction Details

Conductor

ElementNumber of ElementSizeStrandingMaterial
Pair(s)118 AWG7x26TC - Tinned Copper

Insulation

ElementMaterialNom. ThicknessColor Code
Pair(s)PP - Polypropylene0.022 in (0.56 mm)Blue & Orange

Outer Shield

Shield TypeMaterialCoverageDrainwire Type
TapeBi-Laminate (Alum+Poly)100%20 AWG (7x28) TC

Inner Jacket

MaterialNom. Diameter
PVC - Polyvinyl Chloride0.280 in (7.11 mm)

Armor

Armor Type & Material
AIA - Aluminum Interlock Armor

Outer Jacket

MaterialNom. ThicknessNom. Diameter
PVC - Polyvinyl Chloride0.045 in (1.1 mm)0.585 in (14.9 mm)
Overall Cable Diameter (Nominal)0.585 in (14.9 mm)

Electrical Characteristics

Electricals

ElementNom. Conductor DCRNom. Capacitance Cond-to-ShieldNom. Characteristic ImpedenceNom. Velocity of Prop.Max. Current
Pair(s)5.86 Ohm/1000ft (19.2 Ohm/km)45 pF/ft100 Ohm66%5.2 Amps per Conductor
Nom. Outer Shield DCR7.5 Ohm/1000ft (25 Ohm/km)

High Frequency (Nominal/Typical)

ElementFrequency [MHz]Nom. Insertion Loss (Attenuation)
Pair(s)0.0390.08 dB/100ft

High Frequency

Frequency [MHz]Max. Insertion Loss (Attenuation)
0.0310.091 dB/100ft

Voltage

UL Voltage Rating
300 V (CM, PLTC)

Mechanical Characteristics

Temperature

UL TemperatureOperating
105°C-40°C to +105°C

Bend Radius

Stationary Min.Installation Min.
6 in (150 mm)6 in
Max. Pull Tension60 lbs (27 kg)
Bulk Cable Weight38 lbs/1000ft (57 kg/km)

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, Burial
Flammability / Reaction to FireUL1666 Riser, FT4, 1202
CPR ComplianceCPR Euroclass: Eca
NEC / UL ComplianceArticle 725, Article 800
CEC / C(UL) ComplianceCMG HLBCD
IEEE Compliance1202, IEEE 383 Vertical Tray Flame Test (70,000 BTU)
ISO/IEC ComplianceIEC 61158-2
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
UK Regulation ComplianceUKCA Mark
APAC ComplianceChina RoHS II (GB/T 26572-2011)
Other Standard Compliance(s)ISA/SP-50 Type A

Product Notes

NotesFieldbus: Orange jacket. Profibus PA: Intrinsically Safe Blue jacket. Jacket diameter tolerance: +/- .010

History

Update and RevisionRevision Number: 0.81 Revision Date: 05-05-2023
View AllClose