DeviceBus® for ODVA DeviceNet™, 2 Pair 15+18AWG (19x27+19x30) Tinned Copper, PVC+Foam PE Insulation, Individual Beldfoil® & OA Tinned Copper Braid(65%) Shield, PVC Inner Jacket, Aluminum Interlock Armor, PVC Outer Jacket, CM PLTC
Specifications
Specifications
Product Overview
| Suitable Applications | exposure to rodent, crush, or cut through force, harsh environment, ODVA device-level communication, used with CIP (common Industrial Protocol) for control, configuration, and data collection between devices, such as sensors and actuators, and higher level devices such as PLC, and PC in industrial automation, bus topology, etc. |
|---|
Construction Details
Conductor
| Element | Number of Element | Size | Stranding | Material |
|---|
| Power Pair(s) | 1 | 15 AWG | 19x27 | TC - Tinned Copper |
| Data Pair(s) | 1 | 18 AWG | 19x30 | TC - Tinned Copper |
Insulation
| Element | Material | Nom. Thickness | Color Code | Notes |
|---|
| Power Pair(s) | PVC - Polyvinyl Chloride | 0.021 in (0.53 mm) | Red & Black | |
| Data Pair(s) | PE - Polyethylene (Foam) | 0.053 in (1.3 mm) | Blue & White | HDPE |
Inner Shield
| Element | Shield Type | Material | Coverage |
|---|
| Power Pair(s) | Tape | Bi-Laminate (Alum+Poly) | 100% |
| Data Pair(s) | Tape | Bi-Laminate (Alum+Poly) | 100% |
Outer Shield
| Shield Type | Material | Coverage | Drainwire Type |
|---|
| Braid | Tinned Copper (TC) | 65% | 18 AWG (19x30) TC |
Inner Jacket
| Material | Nom. Thickness | Nom. Diameter |
|---|
| PVC - Polyvinyl Chloride | 0.06 in (1.5 mm) | 0.480 in (12.2 mm) |
Armor
| Armor Type & Material |
|---|
| AIA - Aluminum Interlock Armor |
Outer Jacket
| Material | Nom. Thickness | Nom. Diameter |
|---|
| PVC - Polyvinyl Chloride | 0.050 in (1.3 mm) | 0.783 in (19.9 mm) |
| Overall Cable Diameter (Nominal) | 0.783 in (19.9 mm) |
|---|
Electrical Characteristics
Electricals
| Element | Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Nom. Characteristic Impedence | Nom. Velocity of Prop. | Max. Current |
|---|
| Power Pair(s) | 3.6 Ohm/1000ft (12 Ohm/km) | | | | 8 Amps per Conductor |
| Data Pair(s) | 6.9 Ohm/1000ft (23 Ohm/km) | 12 pF/ft (39 pF/m) | 120 Ohm | 75% | |
| Nom. Outer Shield DCR | 1.8 Ohm/1000ft (5.9 Ohm/km) |
|---|
High Frequency
Voltage
| UL Voltage Rating |
|---|
| 300 V (CM, PLTC) |
Mechanical Characteristics
Temperature
| UL Temperature | Operating |
|---|
| 75°C | -20°C to 75°C |
Standards and Compliance
| Environmental Suitability | Indoor, Outdoor, Sunlight Resistance |
|---|
| Flammability / Reaction to Fire | UL 1685 UL Loading |
|---|
| NEC / UL Compliance | Article 725, Article 800, CM, PLTC |
|---|
| CEC / C(UL) Compliance | CMG HLBCD |
|---|
| European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
|---|
| APAC Compliance | China RoHS II (GB/T 26572-2011) |
|---|
| Other Standard Compliance(s) | ODVA Class 2 Thick |
|---|
History
| Update and Revision | Revision Number: 0.243 Revision Date: 05-05-2023 |
|---|
Documentation
Product Bulletins
Catalogs
Brochures
Compliance Documentation
Data Sheets