Belden

123109A - RS485, 4 Pr #22 Str TC, PE Ins, OS+TC Brd, PVC Jkt, AIA Armor, PVC Jkt, CM, PLTC

(No reviews yet) Write a Review
SKU:
123109A
Shipping:
Calculated at Checkout
$0.00

Description

RS-485, 4 Pair 22AWG (7x30) Tinned Copper, PE Insulation, Overall Beldfoil®+Tinned Copper Braid(65%) Shield, PVC Inner Jacket, Aluminum Interlock Armor, PVC Outer Jacket, CM, PLTC

Specifications

Specifications

Product Overview

Suitable Applicationsexposure to rodent, crush, or cut through force, burial, serial communication (RS-485 standard) comprising of PLCs, VFDs, HMIs, motors, RTU, SCADA, etc. within noisy environments over long distance, outdoor such as solar, lighting, etc.

Construction Details

Conductor

ElementNumber of ElementSizeStrandingMaterial
Pair(s)422 AWG7x30TC - Tinned Copper

Insulation

ElementMaterialNom. ThicknessNom. Insulation DiameterColor CodeNotes
Pair(s)PE - Polyethylene (Foam)0.023 in (0.58 mm)0.075 in (1.9 mm)White/Blue Stripe & Blue/White Stripe, White/Orange Stripe & Orange/White Stripe, White/Green Stripe & Green/White Stripe, White/Brown Stripe & Brown/White StripeHDPE

Outer Shield

Shield TypeMaterialCoverageDrainwire Type
TapeBi-Laminate (Alum+Poly)100%22 AWG (7x30) TC
BraidTinned Copper (TC)65%

Inner Jacket

MaterialNom. ThicknessNom. Diameter
PVC - Polyvinyl Chloride0.053 in (1.3 mm)0.448 in (11.4 mm)

Armor

Armor Type & Material
AIA - Aluminum Interlock Armor

Outer Jacket

MaterialNom. ThicknessNom. Diameter
PVC - Polyvinyl Chloride0.050 in (1.3 mm)0.744 in (18.9 mm)
Overall Cable Diameter (Nominal)0.744 in (18.9 mm)

Electrical Characteristics

Electricals

ElementNom. Conductor DCRNom. Capacitance Cond-to-CondNom. Characteristic ImpedenceNom. Velocity of Prop.Max. Current
Pair(s)14.7 Ohm/1000ft (48.2 Ohm/km)11 pF/ft (36 pF/m)120 Ohm78%2.7 Amps per Conductor at 25ºC
Nom. Outer Shield DCR2.53 Ohm/1000ft (8.30 Ohm/km)

High Frequency (Nominal/Typical)

ElementFrequency [MHz]Nom. Insertion Loss (Attenuation)
Pair(s)10.5 dB/100ft

Voltage

UL Voltage Rating
300 V (CM, PLTC)

Mechanical Characteristics

Temperature

UL TemperatureOperating
60°C-40°C to +60°C
Table Notes-40C

Bend Radius

Stationary Min.Installation Min.
7.5 in (190 mm)7.5 in
Max. Pull Tension250 lbs (110 kg)
Bulk Cable Weight233 lbs/1000ft (347 kg/km)

Standards and Compliance

Environmental SuitabilityIndoor, Sunlight Resistance
Flammability / Reaction to FireUL1685 UL Loading, 1202
NEC / UL ComplianceArticle 725, Article 800
CEC / C(UL) ComplianceCMG HLBCD
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)

History

Update and RevisionRevision Number: 0.74 Revision Date: 05-05-2023
View AllClose