Audio, Control & Instrument Cable, 4-22 AWG Solid Bare Copper Conductors, Polyolefin Insulated, PVC Jacket, CM Rated
Specifications
Specifications
Product Overview
Suitable Applications | low voltage analog signals (4-20ma, 0-10v, ...); low voltage control (24v, …); line level audio; voice communications; panel wiring |
---|
Construction Details
Conductor
Element | Number of Element | Size | Stranding | Material |
---|
Conductor(s) | 4 | 22 AWG | Solid | BC - Bare Copper |
Insulation
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|
Conductor(s) | PO - Polyolefin | 0.009 in (0.23 mm) | 0.0433 in mm | Green, Red, Yellow, Black |
Outer Shield
Outer Jacket
Material | Nom. Thickness | Nom. Diameter |
---|
PVC - Polyvinyl Chloride | 0.025 in (0.64 mm) | 0.154 in (3.91 mm) |
Overall Cable Diameter (Nominal) | 0.154 in (3.91 mm) |
---|
Electrical Characteristics
Electricals
Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Nom. Velocity of Prop. | Max. Current |
---|
17.8 Ohm/1000ft | 15 pF/ft (49 pF/m) | 66% | 2.2 Amps per Conductor at 25ºC |
Voltage
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|
60°C | -20°C to +60°C |
Bend Radius
Stationary Min. | Installation Min. |
---|
1.54 in (39.1 mm) | 1.54 in (39.1 mm) |
Max. Pull Tension | 32 lbs (15 kg) |
---|
Bulk Cable Weight | 15 lbs/1000ft |
---|
Standards and Compliance
Environmental Suitability | Indoor - Riser, Indoor |
---|
Flammability / Reaction to Fire | UL 1685 UL Loading, UL 1685 Vertical Tray, IEC 60332-1-2 |
---|
CPR Compliance | CPR Euroclass: Eca |
---|
NEC / UL Compliance | Article 800, CM |
---|
CEC / C(UL) Compliance | CM |
---|
Data Category | Category 3 |
---|
UK Regulation Compliance | UKCA Mark |
---|
History
Update and Revision | Revision Number: 0.400 Revision Date: 03-04-2023 |
---|
Documentation
Brochures and Guides
All Resources
Compliance Documentation
Data Sheets