Fieldbus, 1 Pair 18AWG (7x26) Tinned Copper, PP insulation, Overall Beldfoil® Shield, PVC Inner Jacket, Steel Interlock Armor, PVC Outer Jacket, ISA/SP-50 Type A, PLTC, CM
Specifications
Specifications
Product Overview
| Suitable Applications | exposure to rodent, crush, or cut through force, harsh environment digital and serial two-way communication, oil and gas extraction and refining sites, petrochemical, Profibus process automation or Foundation FieldBus process automation, extreme temperature enviornments, exposure to humidity/moisture, dust, and oil, remote locations long distance applications, etc. |
|---|
Construction Details
Conductor
| Element | Number of Element | Size | Stranding | Material |
|---|
| Pair(s) | 1 | 18 AWG | 7x26 | TC - Tinned Copper |
Insulation
| Element | Material | Nom. Thickness | Color Code |
|---|
| Pair(s) | PP - Polypropylene | 0.022 in (0.56 mm) | Blue & Orange |
Outer Shield
| Shield Type | Material | Coverage | Drainwire Type |
|---|
| Tape | Bi-Laminate (Alum+Poly) | 100% | 20 AWG (7x28) TC |
Inner Jacket
| Material | Nom. Diameter |
|---|
| PVC - Polyvinyl Chloride | 0.280 in (7.11 mm) |
Armor
| Armor Type & Material |
|---|
| SIA - Steel Interlock Armor |
Outer Jacket
| Material | Nom. Thickness | Nom. Diameter |
|---|
| PVC - Polyvinyl Chloride | 0.045 in (1.1 mm) | 0.572 in (14.5 mm) |
| Overall Cable Diameter (Nominal) | 0.572 in (14.5 mm) |
|---|
Electrical Characteristics
Electricals
| Element | Nom. Conductor DCR | Nom. Capacitance Cond-to-Shield | Nom. Characteristic Impedence | Nom. Velocity of Prop. | Max. Current |
|---|
| Pair(s) | 5.86 Ohm/1000ft (19.2 Ohm/km) | 45 pF/ft | 100 Ohm | 66% | 5.2 Amps per Conductor |
| Nom. Outer Shield DCR | 7.5 Ohm/1000ft (25 Ohm/km) |
|---|
High Frequency (Nominal/Typical)
| Element | Frequency [MHz] | Nom. Insertion Loss (Attenuation) |
|---|
| Pair(s) | 0.039 | 0.08 dB/100ft |
High Frequency
| Frequency [MHz] | Max. Insertion Loss (Attenuation) |
|---|
| 0.031 | 0.091 dB/100ft |
Voltage
| UL Voltage Rating |
|---|
| 300 V (CM, PLTC) |
Mechanical Characteristics
Temperature
| UL Temperature | Operating |
|---|
| 105°C | -40°C to +105°C |
| Max. Pull Tension | 200 lbs (91 kg) |
|---|
| Bulk Cable Weight | 288 lbs/1000ft (429 kg/km) |
|---|
Standards and Compliance
| Environmental Suitability | Indoor, Outdoor, Sunlight Resistance |
|---|
| CPR Compliance | CPR Euroclass: Eca |
|---|
| NEC / UL Compliance | Article 725, Article 800 |
|---|
| CEC / C(UL) Compliance | CMG HLBCD |
|---|
| European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
|---|
| UK Regulation Compliance | UKCA Mark |
|---|
| Other Standard Compliance(s) | ISA/SP-50 Type A |
|---|
Product Notes
| Notes | Fieldbus: Orange jacket. Profibus PA: Intrinsically Safe Blue jacket. Jacket diameter tolerance: +/- .010 |
|---|
History
| Update and Revision | Revision Number: 0.74 Revision Date: 05-05-2023 |
|---|
Documentation
Product Bulletins
Technical Resources
Webinars
Training
Compliance Documentation
Data Sheets