Profibus, 1 Pair 22AWG (Solid) Bare Copper, PE Insulation, Overall Beldfoil®+Tinned Copper Braid(65%) Shield, PVC Inner Jacket, Steel Interlock Armor, PVC Outer Jacket, PLTC CM SUN RES Profibus DP
Specifications
Specifications
Product Overview
Suitable Applications | exposure to rodent, crush, or cut through force, harsh environment, outdoors, data transmission applications such as Profibus DP or PA, Instrumentation and computer cable, etc. exposure to temperature extremes, humidity/moisture, dust, and oil. |
---|
Construction Details
Conductor
Element | Number of Element | Size | Stranding | Material |
---|
Pair(s) | 1 | 22 AWG | Solid | BC - Bare Copper |
Insulation
Element | Material | Nom. Thickness | Color Code | Notes |
---|
Pair(s) | PE - Polyethylene (Foam) | 0.035 in (0.89 mm) | Red & Green | Flame Retardant, Foam w/ skin |
Outer Shield
Shield Type | Material | Coverage |
---|
Tape | Bi-Laminate (Alum+Poly) | 100% |
Braid | Tinned Copper (TC) | 65% |
Inner Jacket
Material | Nom. Diameter |
---|
PVC - Polyvinyl Chloride | 0.315 in (8.00 mm) |
Armor
Armor Type & Material |
---|
SIA - Steel Interlock Armor |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter |
---|
PVC - Polyvinyl Chloride | 0.045 in (1.1 mm) | 0.608 in (15.4 mm) |
Overall Cable Diameter (Nominal) | 0.608 in (15.4 mm) |
---|
Electrical Characteristics
Electricals
Element | Nom. Conductor DCR | Nom. Characteristic Impedence | Nom. Velocity of Prop. | Max. Current |
---|
Pair(s) | 16 Ohm/1000ft (52 Ohm/km) | 150 Ohm | 78% | 2.3 Amps per Conductor |
Nom. Outer Shield DCR | 3.9 Ohm/1000ft (13 Ohm/km) |
---|
High Frequency (Nominal/Typical)
Element | Frequency [MHz] | Nom. Insertion Loss (Attenuation) |
---|
Pair(s) | 0.2 | 0.27 dB/100ft |
| 4 | 0.67 dB/100ft |
| 16 | 1.37 dB/100ft |
High Frequency
Frequency [MHz] | Max. Insertion Loss (Attenuation) |
---|
0.2 | 1.1 dB/100m (0.34 dB/100ft) |
4 | 2.65 dB/100m (0.808 dB/100ft) |
16 | 5.4 dB/100m (1.6 dB/100ft) |
Voltage
UL Voltage Rating |
---|
300 V (CM, PLTC) |
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|
60°C | -30°C to +75°C |
Max. Pull Tension | 200 lbs (91 kg) |
---|
Bulk Cable Weight | 356 lbs/1000ft (530 kg/km) |
---|
Standards and Compliance
Environmental Suitability | Indoor, Sunlight Resistance |
---|
NEC / UL Compliance | Article 725, Article 800 |
---|
CEC / C(UL) Compliance | CMG, HLBCD |
---|
European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
---|
APAC Compliance | China RoHS II (GB/T 26572-2011) |
---|
History
Update and Revision | Revision Number: 0.70 Revision Date: 05-05-2023 |
---|
Documentation
Product Bulletins
Technical Resources
Webinars
Training
Data Sheets