DeviceBus® for ODVA DeviceNet™, 2 Pair 15+18AWG (19x27+19x30) Tinned Copper, PVC+Foam PE Insulation, Individual Beldfoil® & OA Tinned Copper Braid(65%) Shield, PVC Inner Jacket, Steel Interlock Armor, PVC Outer Jacket, CM PLTC
Specifications
Specifications
Product Overview
| Suitable Applications | exposure to rodent, crush, or cut through force, harsh environment, ODVA device-level communication, used with CIP (common Industrial Protocol) for control, configuration, and data collection between devices, such as sensors and actuators, and higher level devices such as PLC, and PC in industrial automation, bus topology, etc. |
|---|
Construction Details
Conductor
| Element | Number of Element | Size | Stranding | Material |
|---|
| Power Pair(s) | 1 | 15 AWG | 19x27 | TC - Tinned Copper |
| Data Pair(s) | 1 | 18 AWG | 19x30 | TC - Tinned Copper |
Insulation
| Element | Material | Nom. Thickness | Color Code | Notes |
|---|
| Power Pair(s) | PVC - Polyvinyl Chloride | 0.021 in (0.53 mm) | Red & Black | |
| Data Pair(s) | PE - Polyethylene (Foam) | 0.053 in (1.3 mm) | Blue & White | HDPE |
Inner Shield
| Element | Shield Type | Material | Coverage |
|---|
| Power Pair(s) | Tape | Bi-Laminate (Alum+Poly) | 100% |
| Data Pair(s) | Tape | Bi-Laminate (Alum+Poly) | 100% |
Outer Shield
| Shield Type | Material | Coverage | Drainwire Type |
|---|
| Braid | Tinned Copper (TC) | 65% | 18 AWG (19x30) TC |
Inner Jacket
| Material | Nom. Thickness | Nom. Diameter |
|---|
| PVC - Polyvinyl Chloride | 0.060 in (1.5 mm) | 0.480 in (12.2 mm) |
Armor
| Armor Type & Material |
|---|
| SIA - Steel Interlock Armor |
Outer Jacket
| Material | Nom. Thickness | Nom. Diameter |
|---|
| PVC - Polyvinyl Chloride | 0.050 in (1.3 mm) | 0.770 in (19.6 mm) |
| Overall Cable Diameter (Nominal) | 0.770 in (19.6 mm) |
|---|
Electrical Characteristics
Electricals
| Element | Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Nom. Characteristic Impedence | Nom. Velocity of Prop. | Max. Current |
|---|
| Power Pair(s) | 3.6 Ohm/1000ft (12 Ohm/km) | | | | 8 Amps per Conductor |
| Data Pair(s) | 6.9 Ohm/1000ft (23 Ohm/km) | 12 pF/ft (39 pF/m) | 120 Ohm | 75% | 5 Amps per Conductor |
| Nom. Outer Shield DCR | 1.8 Ohm/1000ft (5.9 Ohm/km) |
|---|
High Frequency
| Element | Frequency [MHz] | Max. Insertion Loss (Attenuation) |
|---|
| Data Pair(s) | 0.125 | 0.13 dB/100ft |
| 0.5 | 0.25 dB/100ft |
| 1 | 0.36 dB/100ft |
Voltage
| UL Voltage Rating |
|---|
| 300 V (CM, PLTC) |
Mechanical Characteristics
Temperature
| UL Temperature | Operating |
|---|
| 75°C | -20°C to +75°C |
| Max. Pull Tension | 200 lbs (91 kg) |
|---|
| Bulk Cable Weight | 498 lbs/1000ft (741 kg/km) |
|---|
Standards and Compliance
| Environmental Suitability | Indoor, Outdoor, Sunlight Resistance |
|---|
| CPR Compliance | CPR Euroclass: Eca |
|---|
| NEC / UL Compliance | Article 725, Article 800 |
|---|
| CEC / C(UL) Compliance | CMG HLBCD |
|---|
| European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
|---|
| UK Regulation Compliance | UKCA Mark |
|---|
| APAC Compliance | China RoHS II (GB/T 26572-2011) |
|---|
Product Notes
| Notes | Thick. Meter marks on jacket to aid users in installation. ODVA DeviceNet is an Open DeviceNet Vendor Associatio, Inc. Trademark. Jacket printed ""1PR16"" instead of ""1PR15"" due to UL requirements for CMG Listing. |
|---|
History
| Update and Revision | Revision Number: 0.75 Revision Date: 05-05-2023 |
|---|
Documentation
Product Bulletins
Technical Resources
Webinars
Training
Compliance Documentation
Data Sheets