DeviceBus® for ODVA DeviceNet™, 2 Pair 15+18AWG (19x27+19x30) Tinned Copper, PVC+Foam PE Insulation, Individual Beldfoil® & OA Tinned Copper Braid(65%) Shield, PVC Inner Jacket, Steel Interlock Armor, PVC Outer Jacket, CM PLTC
Specifications
Specifications
Product Overview
Suitable Applications | exposure to rodent, crush, or cut through force, harsh environment, ODVA device-level communication, used with CIP (common Industrial Protocol) for control, configuration, and data collection between devices, such as sensors and actuators, and higher level devices such as PLC, and PC in industrial automation, bus topology, etc. |
---|
Construction Details
Conductor
Element | Number of Element | Size | Stranding | Material |
---|
Power Pair(s) | 1 | 15 AWG | 19x27 | TC - Tinned Copper |
Data Pair(s) | 1 | 18 AWG | 19x30 | TC - Tinned Copper |
Insulation
Element | Material | Nom. Thickness | Color Code | Notes |
---|
Power Pair(s) | PVC - Polyvinyl Chloride | 0.021 in (0.53 mm) | Red & Black | |
Data Pair(s) | PE - Polyethylene (Foam) | 0.053 in (1.3 mm) | Blue & White | HDPE |
Inner Shield
Element | Shield Type | Material | Coverage |
---|
Power Pair(s) | Tape | Bi-Laminate (Alum+Poly) | 100% |
Data Pair(s) | Tape | Bi-Laminate (Alum+Poly) | 100% |
Outer Shield
Shield Type | Material | Coverage | Drainwire Type |
---|
Braid | Tinned Copper (TC) | 65% | 18 AWG (19x30) TC |
Inner Jacket
Material | Nom. Thickness | Nom. Diameter |
---|
PVC - Polyvinyl Chloride | 0.060 in (1.5 mm) | 0.480 in (12.2 mm) |
Armor
Armor Type & Material |
---|
SIA - Steel Interlock Armor |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter |
---|
PVC - Polyvinyl Chloride | 0.050 in (1.3 mm) | 0.770 in (19.6 mm) |
Overall Cable Diameter (Nominal) | 0.770 in (19.6 mm) |
---|
Electrical Characteristics
Electricals
Element | Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Nom. Characteristic Impedence | Nom. Velocity of Prop. | Max. Current |
---|
Power Pair(s) | 3.6 Ohm/1000ft (12 Ohm/km) | | | | 8 Amps per Conductor |
Data Pair(s) | 6.9 Ohm/1000ft (23 Ohm/km) | 12 pF/ft (39 pF/m) | 120 Ohm | 75% | 5 Amps per Conductor |
Nom. Outer Shield DCR | 1.8 Ohm/1000ft (5.9 Ohm/km) |
---|
High Frequency
Element | Frequency [MHz] | Max. Insertion Loss (Attenuation) |
---|
Data Pair(s) | 0.125 | 0.13 dB/100ft |
| 0.5 | 0.25 dB/100ft |
| 1 | 0.36 dB/100ft |
Voltage
UL Voltage Rating |
---|
300 V (CM, PLTC) |
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|
75°C | -20°C to +75°C |
Max. Pull Tension | 200 lbs (91 kg) |
---|
Bulk Cable Weight | 498 lbs/1000ft (741 kg/km) |
---|
Standards and Compliance
Environmental Suitability | Indoor, Outdoor, Sunlight Resistance |
---|
CPR Compliance | CPR Euroclass: Eca |
---|
NEC / UL Compliance | Article 725, Article 800 |
---|
CEC / C(UL) Compliance | CMG HLBCD |
---|
European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
---|
UK Regulation Compliance | UKCA Mark |
---|
APAC Compliance | China RoHS II (GB/T 26572-2011) |
---|
Product Notes
Notes | Thick. Meter marks on jacket to aid users in installation. ODVA DeviceNet is an Open DeviceNet Vendor Associatio, Inc. Trademark. Jacket printed ""1PR16"" instead of ""1PR15"" due to UL requirements for CMG Listing. |
---|
History
Update and Revision | Revision Number: 0.75 Revision Date: 05-05-2023 |
---|
Documentation
Product Bulletins
Technical Resources
Webinars
Training
Compliance Documentation
Data Sheets