Fieldbus, 2 Pair 18AWG (7x26) Tinned Copper, PO Insulation, Individual & Overall Beldfoil® Shield, Orange PVC Outer Jacket, 600V TC-ER
Specifications
Specifications
Product Overview
Suitable Applications | harsh environment digital and serial two-way communication, oil and gas extraction and refining sites, petrochemical, Profibus process automation or Foundation FieldBus process automation, extreme temperature environments, exposure to humidity/moisture, dust, and oil, remote locations long distance applications, etc. |
---|
Physical Characteristics (Overall)
Conductor
Element | AWG | Stranding | Material | No. of Conductors | No. of Pairs |
---|
Pair(s) | 18 | 7x26 | TC - Tinned Copper | | 2 |
Ground Wire | 18 | 7x26 | TC - Tinned Copper | 1 | |
Insulation
Element | Material |
---|
| PVC - Polyvinyl Chloride |
Ground Wire | PP - Polypropylene |
Color Chart
Number | Color |
---|
1 | Blue, Orange and Numbered |
2 | |
3 | |
Color Chart 2
Inner Shield
Type | Material | Material Trade Name | Coverage [%] | Drainwire AWG | Drainwire Construction n x D |
---|
Tape | Bi-Laminate (Alum+Poly) | Beldfoil® | 100% | 18 | 7x26 |
| Tinned Copper (TC) | | | | |
Outer Shield
Type | Material | Material Trade Name | Coverage [%] | Drainwire Material | Drainwire AWG | Drainwire Construction n x D |
---|
Tape | Bi-Laminate (Alum+Poly) | Beldfoil® | 100% | TC - Tinned Copper | 20 | 7x28 |
Outer Jacket
Material | Nominal Diameter |
---|
PVC - Polyvinyl Chloride | 0.51 in |
Electrical Characteristics
Conductor DCR
Individual Pair Nominal Shield DCR | Nominal Conductor DCR |
---|
7.5 Ohm/1000ft | 5.86 Ohm/1000ft |
Capacitance
Max. Capacitance Unbalance | Nom. Capacitance Conductor to Other Conductor to Shield | Nom.Mutual Capacitance |
---|
1.2 pF/ft | 45 pF/ft | 24 pF/ft |
Inductance
Nominal Inductance |
---|
0.22 µH/ft |
Impedance
Nominal Characteristic Impedance |
---|
100 Ohm |
High Frequency (Nominal/Typical)
Nom. Insertion Loss |
---|
0.08 dB/100ft |
High Frequency
Frequency [MHz] | Max. Insertion Loss (Attenuation) | Max./Min. Input Impedance (unFitted) |
---|
0.031 MHz | 0.091 dB/100ft | 100 Ohm |
Current
Element | Max. Recommended Current [A] |
---|
Per Conductor | 5.2 Amps per Conductor |
Voltage
UL Voltage Rating |
---|
600 V RMS |
Electrical Characteristics Notes | Max. Propagation Delay Change From 7.812 kHz to 39.06 kHz: 518 pS/ft |
---|
Other Electrical Characteristic 2 | 31.25 KBits/sec |
---|
Temperature Range
UL Temp Rating | 75°C |
---|
Operating Temperature Range | -30°C to +75°C |
---|
Mechanical Characteristics
Max. Pull Tension | 112 lbs |
---|
Min. Bend Radius/Minor Axis | 5.1 in |
---|
Standards
NEC Articles | Article 336 |
---|
NEC/(UL) Compliance | TC-ER |
---|
Applicable Environmental and Other Programs
EU Directive 2000/53/EC (ELV) | Yes |
---|
EU Directive 2011/65/EU (RoHS 2) | Yes |
---|
EU Directive 2012/19/EU (WEEE) | Yes |
---|
EU Directive 2015/863/EU (RoHS 2 amendment) | Yes |
---|
EU Directive Compliance | EU Directive 2003/11/EC (BFR) |
---|
EU CE Mark | Yes |
---|
MII Order #39 (China RoHS) | Yes |
---|
Suitability
Suitability - Indoor | Yes |
---|
Suitability - Oil Resistance | Yes |
---|
Suitability - Outdoor | Yes |
---|
Suitability - Sunlight Resistance | Yes |
---|
Flammability, LS0H, Toxicity Testing
UL Flammability | UL1685 UL Loading |
---|
UL voltage rating | 600 V RMS |
---|
Plenum/Non-Plenum
History
Update and Revision | Revision Number: 0.451 Revision Date: 05-05-2023 |
---|
Documentation
Product Bulletins
Catalogs
Brochures
Data Sheets