Belden

1340A - Fieldbus, 8 Pr #18 Str TC, PO Ins, IS/OS, PVC Jkt, 600V TC-ER

(No reviews yet) Write a Review
SKU:
1340A
Shipping:
Calculated at Checkout
$0.00

Description

Fieldbus, 8 Pair 18AWG (7x26) Tinned Copper, PO Insulation, Individual & Overall Beldfoil® Shield, Orange PVC Outer Jacket, 600V TC-ER

Specifications

Specifications

Product Overview

Suitable Applicationsharsh environment digital and serial two-way communication, oil and gas extraction and refining sites, petrochemical, Profibus process automation or Foundation FieldBus process automation, extreme temperature environments, exposure to humidity/moisture, dust, and oil, remote locations long distance applications, etc.

Physical Characteristics (Overall)

Conductor

ElementAWGStrandingMaterialNo. of ConductorsNo. of Pairs
Pair(s)187x26TC - Tinned Copper8
Ground Wire187x26TC - Tinned Copper1
Conductor Count17

Insulation

ElementMaterial
PVC - Polyvinyl Chloride
Ground WirePVC - Polyvinyl Chloride

Color Chart

NumberColor
1Blue, Orange and Numbered
2
3
4
5
6
7
8
9

Color Chart 2

Color
Green/Yellow

Inner Shield

TypeMaterialMaterial Trade NameCoverage [%]Drainwire AWGDrainwire Construction n x D
TapeBi-Laminate (Alum+Poly)Beldfoil®100%187x26
Tinned Copper (TC)

Outer Shield

TypeMaterialMaterial Trade NameCoverage [%]Drainwire MaterialDrainwire AWGDrainwire Construction n x D
TapeBi-Laminate (Alum+Poly)Beldfoil®100%TC - Tinned Copper207x28

Outer Jacket

MaterialNominal Diameter
PVC - Polyvinyl Chloride0.81 in

Electrical Characteristics

Conductor DCR

Individual Pair Nominal Shield DCRNominal Conductor DCR
7.5 Ohm/1000ft5.86 Ohm/1000ft

Capacitance

Max. Capacitance UnbalanceNom. Capacitance Conductor to Other Conductor to ShieldNom.Mutual Capacitance
1.2 pF/ft45 pF/ft24 pF/ft

Inductance

Nominal Inductance
0.22 µH/ft

Impedance

Nominal Characteristic Impedance
100 Ohm

High Frequency (Nominal/Typical)

Nom. Insertion Loss
0.08 dB/100ft

High Frequency

Frequency [MHz]Max. Insertion Loss (Attenuation)Max./Min. Input Impedance (unFitted)
0.031 MHz0.091 dB/100ft100 Ohm

Current

ElementMax. Recommended Current [A]
Per Conductor5.2 Amps per Conductor

Voltage

UL Voltage Rating
600 V RMS
Electrical Characteristics NotesMax. Propagation Delay Change From 7.812 kHz to 39.06 kHz: 518 pS/ft
Other Electrical Characteristic 231.25 kBits/sec

Temperature Range

UL Temp Rating75°C
Operating Temperature Range-30°C to +75°C

Mechanical Characteristics

Oil ResistanceYes
UV ResistanceYes
Max. Pull Tension381 lbs
Min. Bend Radius/Minor Axis8.1 in

Standards

NEC ArticlesArticle 336
NEC/(UL) ComplianceTC-ER

Applicable Environmental and Other Programs

EU Directive 2000/53/EC (ELV)Yes
EU Directive 2011/65/EU (RoHS 2)Yes
EU Directive 2012/19/EU (WEEE)Yes
EU Directive 2015/863/EU (RoHS 2 amendment)Yes
EU Directive ComplianceEU Directive 2003/11/EC (BFR)
EU CE MarkYes
MII Order #39 (China RoHS)Yes

Suitability

Suitability - IndoorYes
Suitability - Oil ResistanceYes
Suitability - OutdoorYes
Suitability - Sunlight ResistanceYes

Flammability, LS0H, Toxicity Testing

UL FlammabilityUL1685 UL Loading
UL voltage rating600 V RMS

Plenum/Non-Plenum

Plenum (Y/N)No

Related Part Numbers

FootnoteC - CRATE REEL PUT-UP.

History

Update and RevisionRevision Number: 0.289 Revision Date: 05-05-2023
View AllClose

Additional Information

Variant_Options:
Item #|Color|Put-Up Type|Length|UPC
Variant_Options 1340A 0035000:
1340A 0035000|Orange|Reel|5,000 ft|612825112297
View AllClose