Category 7A Enhanced Premise Horizontal Cable (1250MHz), 4-Pair, 22 AWG solid bare copper conductors, S/FTP, Foam Polyethylene insulation, each pair with Beldfoil® shield, overall tinned copper braid shield (50% coverage), LSZH jacket IEC60332-3-24
Specifications
Specifications
Product Overview
Suitable Applications | Horizontal and building backbone cable; Support current and future Category 6a, 7 and 7a applications, such as: 25GBase-T (25 Gigabit Ethernet), 10GBase - T (10 Gigabit Ethernet), 1000Base - T (Gigabit Ethernet), 100 Base - T, 10 Base - T, FDDI, ATM |
---|
Construction Details
Conductor
Element | Size | Stranding | Material | Number of Pairs | Number of Element |
---|
Individual Shielded Pair | 22 AWG | Solid | BC - Bare Copper | 4 | 8 |
Insulation
Element | Material | Nom. Insulation Diameter | Color Code |
---|
Individual Shielded Pair | PE - Polyethylene (Foam) | 1.6 mm (0.063 in) | White / Blue, White / Orange, White / Green, White / Brown |
Cable Core
Description |
---|
2 twisted insulated conductors with overall foil, 4 pairs all twisted together |
Inner Shield
Element | Shield Type | Material | Coverage |
---|
Individual Shielded Pair | Tape | Bi-Laminate (Alum+Poly) | 100% |
Table Notes | Aluminum facing outside |
---|
Outer Shield
Shield Type | Material | Coverage |
---|
Braid | Tinned Copper (TC) | 50% |
Outer Jacket
Material | Nom. Diameter | Ripcord |
---|
LSZH - Low Smoke Zero Halogen (Flame Retardant) | 8.7 mm (0.34 in) | Yes |
Overall Cable Diameter (Nominal) | 8.7 mm (0.34 in) |
---|
Electrical Characteristics
Electricals
Max. Conductor DCR | Max. Mutual Capacitance | Max. Capacitance Unbalance | Nom. Characteristic Impedance |
---|
95 Ohm/km | 56 pF/m (17 pF/ft) | 160 pF/100m | 100 Ohm |
Delay
Max. Delay Skew | Nom. Velocity of Prop. |
---|
25 ns/100m | 73% |
High Frequency
Frequency [MHz] | Max. Insertion Loss (Attenuation) [dB/100m] | Min. NEXT [dB] | Min. PSNEXT [dB] | Min. ACR [dB] | Min. PSACR [dB] | Min. ACRF (ELFEXT) [dB] | Min. PSACRF (PSELFEXT) [dB] | Min. RL (Return Loss) [dB] | Min. PSANEXT [dB] | Min. PSAACRF [dB] | Min. TCL [dB] | Min. ELTCTL [dB] |
---|
1 | 2.1 | 78 | 75 | 75.9 | 72.9 | 78 | 75 | 20 | 67 | 67 | 40 | 23 |
4 | 3.7 | 78 | 75 | 74.3 | 71.3 | 78 | 75 | 23 | 67 | 67 | 34 | 15 |
10 | 5.8 | 78 | 75 | 72.2 | 69.2 | 75.3 | 72.3 | 25 | 67 | 67 | 30 | 10.9 |
16 | 7.3 | 78 | 75 | 70.7 | 67.7 | 71.2 | 68.2 | 25 | 67 | 67 | 28 | 5.1 |
31.2 | 10.3 | 78 | 75 | 67.7 | 64.7 | 65.4 | 62.4 | 23.6 | 67 | 63.3 | 25.2 | |
62.5 | 14.6 | 78 | 75 | 63.4 | 60.4 | 59.4 | 56.4 | 21.5 | 67 | 57.3 | 22 | |
100 | 18.5 | 75.4 | 72.4 | 56.9 | 53.9 | 55.3 | 52.3 | 20.1 | 67 | 53.2 | 20 | |
155 | 23.2 | 72.5 | 69.5 | 49.3 | 46.3 | 51.5 | 48.5 | 18.8 | 67 | 49.4 | 18.1 | |
250 | 29.7 | 69.4 | 66.4 | 39.7 | 36.7 | 47.3 | 44.3 | 17.3 | 67 | 45.2 | 16 | |
500 | 42.8 | 64.9 | 61.9 | 22.2 | 19.2 | 41.3 | 38.3 | 17.3 | 67 | 39.2 | | |
600 | 47.1 | 63.7 | 60.7 | 16.6 | 13.6 | 39.7 | 36.7 | 17.3 | 65.8 | 37.6 | | |
1000 | 61.9 | 60.4 | 57.4 | | | 35.3 | 32.3 | 15.1 | 62.5 | 33.2 | | |
1250 | 69.9 | 58.9 | 55.9 | | | 33.4 | 30.4 | 14.1 | 61 | 31.3 | | |
Table Notes | Limits below 4 MHz are for information only; Reference standard: IEC 61156-5 |
---|
Transfer Impedance
Frequency | Max. Transfer Impedance |
---|
1 Mhz | Max. 10 mOhm/m |
10 Mhz | Max. 10 mOhm/m |
30 Mhz | Max. 30 mOhm/m |
100 Mhz | Max. 100 mOhm/m |
Transfer Impedance Class | Grade 1 |
---|
Screening Class | Type I |
---|
Table Notes | Coupling Attenuation |
---|
Voltage
Mechanical Characteristics
Temperature
Operating | Installation |
---|
-30°C to +60°C | 0°C To +50°C |
Bend Radius
Stationary Min. | Installation Min. |
---|
35 mm (1.4 in) | 70 mm |
Max. Pull Tension | 105 N (23.6 lbf) |
---|
Bulk Cable Weight | 82 kg/km |
---|
Standards and Compliance
Environmental Suitability | Indoor |
---|
Flammability / Reaction to Fire | IEC 60332-1-2, IEC 60332-3-24 |
---|
IEEE Compliance | PoE: IEEE 802.3bt Type 1, Type 2, Type 3, Type 4 |
---|
Data Category | Category 7A |
---|
TIA/EIA Compliance | ANSI/TIA 568.2-D |
---|
ISO/IEC Compliance | ISO/IEC 11801-1, IEC 61034-2 - Smoke Density Min Transmittance = 60% |
---|
CENELEC Compliance | EN 50173-1, Segregation class according EN50174-2 = d |
---|
European Halogen Free Standards | IEC 62821-1 Halogen Free Compliance = Yes, IEC 60754-1 - Halogen Amount = Zero, IEC 60754-2 - Halogen Acid Gas Amount - Max. Conductivity = 2.5 µS/mm, IEC 60754-2 - Halogen Acid Gas Amount - Min. pH = 4.3 |
---|
European Directive Compliance | EU CE Mark |
---|
Product Notes
Notes | Electrical values are expected performance based on cable testing and representative performance within a typical Belden system. |
---|
History
Update and Revision | Revision Number: 0.263 Revision Date: 03-24-2023 |
---|