Conductor
Element | Number of Element | Size | Stranding | Material |
---|
Conductor(s) | 3 | 16 AWG | 65x34 | BC - Bare Copper |
Insulation
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|
Conductor(s) | EPDM - Ethylene Propylene Diene Monomer | 0.033 in (0.84 mm) | 0.123 in mm | Black, White, Green |
Outer Shield
Outer Jacket
Separator | Material | Nom. Thickness | Nom. Diameter |
---|
Cotton Serve | SBR - Styrene Butadiene Rubber | 0.065 in (1.7 mm) | 0.405 in |
Overall Cable Diameter (Nominal) | 0.405 in |
---|
Electrical Characteristics
Electricals
Nom. Conductor DCR | Max. Current |
---|
4.17 Ohm/1000ft | 10 Amps per Conductor at 25ºC (over 50 ft) |
| 10 Amps per Conductor at 25ºC (over 50 ft) |
Voltage
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|
60°C | -20°C To +60°C |
Bend Radius
Stationary Min. | Installation Min. |
---|
4.05 in (103 mm) | 4.05 in |
Max. Pull Tension | 97.5 lbs (44.2 kg) |
---|
Bulk Cable Weight | 90 lbs/1000ft |
---|
Standards and Compliance
Environmental Suitability | Indoor, Outdoor |
---|
Flammability / Reaction to Fire | FT2 |
---|
NEC / UL Compliance | Article 400, S |
---|
European Directive Compliance | EU CE Mark, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
---|
APAC Compliance | China RoHS II (GB/T 26572-2011) |
---|
History
Update and Revision | Revision Number: 0.396 Revision Date: 05-05-2023 |
---|
Documentation
Catalogs
Tools
Compliance Documentation
Data Sheets