Portable Cordage, 3 Conductor 18AWG (16x30) Bare Copper, EPDM Insulation, Rubber Outer Jacket, UL Type SJ
Specifications
Specifications
Construction Details
Conductor
Element | Number of Element | Size | Stranding | Material |
---|
Conductor(s) | 3 | 18 AWG | 16x30 | BC - Bare Copper |
Insulation
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|
Conductor(s) | EPDM - Ethylene Propylene Diene Monomer | 0.031 in (0.79 mm) | 0.110 in mm | Black, White, Green |
Outer Shield
Outer Jacket
Separator | Material | Nom. Thickness | Nom. Diameter |
---|
Paper Tape | SBR - Styrene Butadiene Rubber | 0.044 in (1.1 mm) | 0.328 in |
Overall Cable Diameter (Nominal) | 0.328 in |
---|
Electrical Characteristics
Electricals
Nom. Conductor DCR | Max. Current |
---|
6.7 Ohm/1000ft | 15 Amps per Conductor at 25ºC (7 Amps over 50 ft) |
| 7 Amps per Conductor at 25ºC (over 50 ft) |
Voltage
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|
60°C | -25°C to 60°C |
Bend Radius
Stationary Min. | Installation Min. |
---|
3.28 in (83.3 mm) | 3.28 in |
Max. Pull Tension | 62.4 lbs (28.3 kg) |
---|
Bulk Cable Weight | 55 lbs/1000ft |
---|
Standards and Compliance
Flammability / Reaction to Fire | FT2 |
---|
NEC / UL Compliance | Article 400, SJ |
---|
European Directive Compliance | EU CE Mark, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
---|
APAC Compliance | China RoHS II (GB/T 26572-2011) |
---|
Product Notes
Notes | Cabling paper separator tape |
---|
History
Update and Revision | Revision Number: 0.392 Revision Date: 05-05-2023 |
---|
Documentation
Catalogs
Tools
Compliance Documentation
Data Sheets