Portable Cordage, 2 Conductor 18AWG (42x34) Bare Copper, PVC Insulation, PVC Outer Jacket, UL Type SJTOW
Specifications
Specifications
Construction Details
Conductor
Element | Number of Element | Size | Stranding | Material |
---|
Conductor(s) | 2 | 18 AWG | 42x34 | BC - Bare Copper |
Insulation
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|
Conductor(s) | PVC - Polyvinyl Chloride | 0.032 in (0.81 mm) | 0.110 in (2.79 mm) | Blue, Brown |
Outer Shield
Outer Jacket
Separator | Material | Nom. Thickness | Nom. Diameter |
---|
Paper Tape | PVC - Polyvinyl Chloride | 0.035 in (0.89 mm) | 0.29 in |
Overall Cable Diameter (Nominal) | 0.29 in |
---|
Electrical Characteristics
Electricals
Nom. Conductor DCR | Max. Current |
---|
6.97 Ohm/1000ft | 10 Amps per Conductor at 25ºC (7 Amps over 50 ft) |
Voltage
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|
105°C Dry, 60°C Wet | -35°C To +60°C Wet/105°C Dry |
Bend Radius
Stationary Min. | Installation Min. |
---|
2.9 in (74 mm) | 2.9 in |
Max. Pull Tension | 41 lbs (19 kg) |
---|
Bulk Cable Weight | 38 lbs/1000ft |
---|
Standards and Compliance
Environmental Suitability | Indoor, Outdoor, Sunlight Resistance, Oil Resistance |
---|
Flammability / Reaction to Fire | VW-1 |
---|
NEC / UL Compliance | Article 400, SJTOW |
---|
AWM Compliance | SJTOW |
---|
CEC / C(UL) Compliance | LL7874 |
---|
European Directive Compliance | EU CE Mark, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
---|
APAC Compliance | China RoHS II (GB/T 26572-2011) |
---|
Product Notes
Notes | Jacket is Oil Resistant |
---|
History
Update and Revision | Revision Number: 0.392 Revision Date: 05-05-2023 |
---|
Documentation
Catalogs
Tools
Compliance Documentation
Data Sheets