Belden

2114A - Fieldbus, 16 Pr #16 Str TC, XLPO Ins, IS/OS, TPE Jkt, CMG

(No reviews yet) Write a Review
SKU:
2114A
Shipping:
Calculated at Checkout
$0.00

Description

Fieldbus, 16 Pair 16AWG (7x24H) Tinned Copper, XLPO Insulation, Individual & Overall Beldfoil® Shield, Orange TPE Outer Jacket, CMG

Specifications

Specifications

Product Overview

Suitable Applicationsharsh environment digital and serial two-way communication, oil and gas extraction and refining sites, petrochemical, Profibus process automation or Foundation FieldBus process automation, extreme temperature environments, exposure to humidity/moisture, dust, and oil, remote locations long distance applications, etc.

Physical Characteristics (Overall)

Conductor

ElementAWGStrandingMaterialNo. of Pairs
Pair(s)167x24TC - Tinned Copper16
Conductor Count32
Total Number of Pairs16

Insulation

MaterialNominal Wall Thickness
XLPE - Cross-Linked Polyethylene (Thermoset)0.038 in

Color Chart

NumberColor
1Blue, Orange and Numbered
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

Inner Shield

TypeMaterialMaterial Trade NameCoverage [%]Drainwire MaterialDrainwire AWG
TapeBi-Laminate (Alum+Poly)Beldfoil®100%TC - Tinned Copper18

Outer Shield

TypeMaterialMaterial Trade NameCoverage [%]Drainwire MaterialDrainwire AWG
TapeBi-Laminate (Alum+Poly)Beldfoil®100%TC - Tinned Copper16

Outer Jacket

MaterialNominal DiameterNominal Wall Thickness
TPE - Thermoplastic Elastomer1.321 in0.085 in

Electrical Characteristics

Conductor DCR

Nominal Conductor DCR
4.2 Ohm/1000ft

Capacitance

Nom. Capacitance Conductor to Conductor
22 pF/ft

Inductance

Nominal Inductance
0.22 µH/ft

Impedance

Nominal Characteristic Impedance
100 Ohm

High Frequency (Nominal/Typical)

Frequency [MHz]Nom. Insertion Loss
0.039 MHz0.065 dB/100ft

Delay

Nominal Velocity of Propagation (VP) [%]
64%

Current

Max. Recommended Current [A]
7.2 Amps per Conductor

Voltage

UL Voltage Rating
300 V
Electrical Characteristics NotesMax Propagation Delay Change From 7.812 kHz to 39.06 kHz: 518 pS/ft
Other Electrical Characteristic 231.25 KBits/sec

Temperature Range

UL Temp Rating90°C
Operating Temperature Range-40°C to 90°C

Mechanical Characteristics

Oil ResistanceYes
Bulk Cable Weight847 lbs/1000ft
Max. Pull Tension1536 lbs
Min. Bend Radius/Minor Axis13.25 in

Standards

NEC ArticlesArticle 725, Article 727, Article 800
NEC/(UL) ComplianceCMG, ITC, PLTC-ER
CEC/C(UL) ComplianceCIC, TC
CSA AWM ComplianceAWM I A/B II A/B
ISO/IEC ComplianceIEC 61158-2
Other StandardsISA/SP-50 Type A

Applicable Environmental and Other Programs

EU Directive 2000/53/EC (ELV)Yes
EU Directive 2003/11/EC (BFR)Yes
EU Directive 2011/65/EU (RoHS 2)Yes
EU Directive 2012/19/EU (WEEE)Yes
EU Directive 2015/863/EU (RoHS 2 amendment)Yes
EU Directive ComplianceEU Directive 2003/11/EC (BFR)
EU CE MarkYes

Suitability

Suitability - BurialYes
Suitability - IndoorYes
Suitability - OutdoorYes
Suitability - Sunlight ResistanceYes

Flammability, LS0H, Toxicity Testing

UL FlammabilityUL1685 UL Loading
IEC FlammabilityIEC 60332-3-24
UL voltage rating300 V RMS

Plenum/Non-Plenum

Plenum (Y/N)No

History

Update and RevisionRevision Number: 0.231 Revision Date: 05-05-2023
View AllClose

Additional Information

Variant_Options:
Item #|Color|Put-Up Type|Length|UPC
Variant_Options 2114A 0061000:
2114A 0061000|Blue, Light|Reel|1,000 ft|612825129387
Variant_Options 2114A 0031000:
2114A 0031000|Orange|Reel|1,000 ft|612825129370
View AllClose