Belden

2118Z - Fieldbus, 1 Pr #18 Str TC, XLPO Ins, OS, LSZH-TS Jkt, 600V TC

(No reviews yet) Write a Review
SKU:
2118Z
Shipping:
Calculated at Checkout
$0.00

Description

Fieldbus, 1 Pair 18AWG (7x26) Tinned Copper, XLPO Insulation, Overall Beldfoil® Shield, LSZH-TS Outer Jacket, 600V TC

Specifications

Specifications

Product Overview

Suitable Applicationsharsh environment digital and serial two-way communication, oil and gas extraction and refining sites, petrochemical, Profibus process automation or Foundation FieldBus process automation, extreme temperature environments, exposure to humidity/moisture, dust, and oil, remote locations long distance applications, etc.

Physical Characteristics (Overall)

Conductor

ElementAWGStrandingMaterialNominal DiameterNo. of Pairs
Pair(s)187x26TC - Tinned Copper0.046 in1
Conductor Count2
Total Number of Pairs1

Insulation

MaterialNominal DiameterNominal Wall Thickness
XLPE - Cross-Linked Polyethylene (Thermoset)0.110 in0.032 in

Color Chart

NumberColor
1Blue & Orange

Outer Shield

TypeMaterialMaterial Trade NameCoverage [%]Drainwire MaterialDrainwire AWG
TapeBi-Laminate (Alum+Poly)Beldfoil®100%TC - Tinned Copper20

Outer Jacket

MaterialNominal DiameterNominal Wall Thickness
LSZH - Low Smoke Zero Halogen (Flame Retardant, Thermoset)0.348 in0.047 in

Electrical Characteristics

Conductor DCR

Nominal Conductor DCR
5.86 Ohm/1000ft

Capacitance

Nom. Capacitance Conductor to Conductor
22.0 pF/ft

Inductance

Nominal Inductance
0.22 µH/ft

High Frequency (Nominal/Typical)

Frequency [MHz]Nom. Insertion Loss
39 kHz0.08 dB/100ft

Delay

Nominal Velocity of Propagation (VP) [%]
64%

High Frequency

Max. Insertion Loss (Attenuation)
0.091 dB/100ft

Voltage

UL DescriptionUL Voltage Rating
TC600 V
UL13091000 V RMS

Temperature Range

Installation Temperature Range-25°C To +90°C
UL Temp Rating90°C Wet/Dry
Operating Temperature Range-40°C to +90°C

Mechanical Characteristics

Bulk Cable Weight56 lbs/1000ft
Max. Pull Tension57 lbs
Min Bend Radius (Overall)3.5 in

Standards

NEC/(UL) ComplianceTC
CPR EuroclassFca

Applicable Environmental and Other Programs

EU Directive 2000/53/EC (ELV)Yes
EU Directive 2011/65/EU (RoHS 2)Yes
EU Directive 2012/19/EU (WEEE)Yes
EU Directive 2015/863/EU (RoHS 2 amendment)Yes
EU Directive ComplianceEU Directive 2002/95/EC (RoHS); EU Directive 2003/11/EC (BFR)
EU CE MarkYes

Suitability

Suitability - IndoorYes
Suitability - OutdoorYes
Suitability - Sunlight ResistanceYes

Flammability, LS0H, Toxicity Testing

IEEE Flammability1202, IEEE 383 Vertical Tray Flame Test (70,000 BTU)

Plenum/Non-Plenum

Plenum (Y/N)No

Product Notes

NotesImpedance 100 Ohm @ 31.25 kHz

History

Update and RevisionRevision Number: 0.222 Revision Date: 05-05-2023
View AllClose

Additional Information

Variant_Options:
Item #|Color|UPC
Variant_Options 2118Z 0105000:
2118Z 0105000|Black|612825129509
View AllClose