Fieldbus, 36 Pair 16AWG (7x24) Tinned Copper, XLPE Insulation, Individual & Overall Beldfoil® Shield, TPE Outer Jacket, 600V TC-ER
Specifications
Specifications
Product Overview
Suitable Applications | harsh environment digital and serial two-way communication, oil and gas extraction and refining sites, petrochemical, Profibus process automation or Foundation FieldBus process automation, extreme temperature environments, exposure to humidity/moisture, dust, and oil, remote locations long distance applications, etc. |
---|
Construction Details
Conductor
Element | Number of Element | Size | Stranding | Material |
---|
Pair(s) | 36 | 16 AWG | 7x24 | TC - Tinned Copper |
Insulation
Element | Material | Nom. Thickness | Color Code |
---|
Pair(s) | XLPE - Cross-Linked Polyethylene (Thermoset) | 0.038 in (0.97 mm) | Blue, Orange and Numbered |
Inner Shield
Element | Shield Type | Material | Coverage | Drainwire Type | Notes |
---|
Pair(s) | Tape | Bi-Laminate (Alum+Poly) | 100% | 18 AWG (7x26) TC | Individually Shielded |
Outer Shield
Shield Type | Material | Coverage | Drainwire Type |
---|
Tape | Bi-Laminate (Alum+Poly) | 100% | 16 AWG (7x24) TC |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter | Ripcord |
---|
TPE - Thermoplastic Elastomer | 0.12 in (3.0 mm) | 1.952 in (49.58 mm) | Yes |
Overall Cable Diameter (Nominal) | 1.952 in (49.58 mm) |
---|
Electrical Characteristics
Electricals
Nom. Conductor DCR | Max. Capacitance Unbalance | Nom. Capacitance Cond-to-Cond | Nom. Characteristic Impedence | Nom. Velocity of Prop. | Max. Current |
---|
4.2 Ohm/1000ft (14 Ohm/km) | 1.2 pF/ft (3.9 pF/m) | 22 pF/ft (72 pF/m) | 100 Ohm | 64% | 7.2 Amps per Conductor |
High Frequency (Nominal/Typical)
Frequency [MHz] | Nom. Insertion Loss (Attenuation) |
---|
0.039 | 0.065 dB/100ft |
High Frequency
Max. Insertion Loss (Attenuation) | Max./Min. Input Impedance (unFitted) |
---|
0.091 dB/100ft | 100 Ohm |
Voltage
UL Voltage Rating |
---|
600 V (TC-ER), 600 V (CSA CIC Type TC) |
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|
90°C Wet/Dry | -40°C to 90°C |
Max. Pull Tension | 3412 lbs (1548 kg) |
---|
Bulk Cable Weight | 1875 lbs/1000ft (2790 kg/km) |
---|
Standards and Compliance
Environmental Suitability | Indoor, Outdoor, Sunlight Resistance, Oil Resistance, Burial |
---|
Flammability / Reaction to Fire | UL1581 Vertical Tray, IEC 60332-3-24 |
---|
NEC / UL Compliance | Article 336, TC-ER |
---|
AWM Compliance | AWM I A/B II A/B |
---|
CEC / C(UL) Compliance | CIC, TC |
---|
ISO/IEC Compliance | IEC 61158-2 |
---|
European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
---|
APAC Compliance | China RoHS II (GB/T 26572-2011) |
---|
Other Standard Compliance(s) | ISA/SP-50 Type A |
---|
History
Update and Revision | Revision Number: 0.265 Revision Date: 05-05-2023 |
---|
Documentation
Product Bulletins
Catalogs
Brochures
Data Sheets