Canadian Instrumentation Cable TC-ACIC 600V, 4 Pair 16AWG (7x24) Tinned Copper, PVC Insulation E1 Color Code, Individual & Overall Beldfoil® Shield, PVC Inner Jacket, Aluminum Interlock Armor, Black PVC Outer Jacket, 105C Dry 75C Wet CSA HLABCD SUN RES -40C
Specifications
Specifications
Construction Details
Conductor
| Element | Number of Element | Size | Stranding | Material | 
|---|
| Pair(s) | 4 | 16 AWG | 7x24 | TC - Tinned Copper | 
Insulation
| Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code | 
|---|
| Pair(s) | PVC - Polyvinyl Chloride | 0.03 in (0.76 mm) | 0.118 in (3.00 mm) | ICEA Chart E1 | 
Inner Shield
| Shield Type | Material | Coverage | Drainwire Type | 
|---|
| Tape | Bi-Laminate (Alum+Poly) | 100% | 18 AWG (7x26) TC | 
Outer Shield
| Shield Type | Material | Coverage | Drainwire Type | 
|---|
| Tape | Bi-Laminate (Alum+Poly) | 100% | 16 AWG (7x24) TC | 
Inner Jacket
| Material | Nom. Thickness | Nom. Diameter | Ripcord | Color | 
|---|
| PVC - Polyvinyl Chloride | 0.063 in (1.6 mm) | 0.673 in (17.1 mm) | Yes | Black | 
Armor
| Armor Type & Material | Armor Thickness | Diameter Over Armor | 
|---|
| AIA - Aluminum Interlock Armor | 0.025 in (0.64 mm) | 0.893 in (22.7 mm) | 
Outer Jacket
| Separator | Material | Nom. Thickness | Nom. Diameter | Ripcord | 
|---|
| Polyester Tape | PVC - Polyvinyl Chloride | 0.052 in (1.3 mm) | 0.997 in | Yes | 
| Overall Cable Diameter (Nominal) | 0.997 in | 
|---|
Electrical Characteristics
Electricals
| Nom. Conductor DCR | Nom. Inner Shield DCR | Max. Current | 
|---|
| 4.2 Ohm/1000ft | 5.4 Ohm/1000ft (18 Ohm/km) | 4.4 Amps per Conductor at 30ºC | 
Voltage
Mechanical Characteristics
Temperature
| Operating | Installation | 
|---|
| Dry: -40°C to +105°C, Wet: -40°C to +75°C | -25°C To +105 | 
Bend Radius
| Stationary Min. | Installation Min. | 
|---|
| 11.96 in (303.8 mm) | 11.96 in | 
| Max. Pull Tension | 200 lbs (91 kg) | 
|---|
| Bulk Cable Weight | 412 lbs/1000ft | 
|---|
Standards and Compliance
| Environmental Suitability | Indoor, Outdoor, Sunlight Resistance, UV Resistance | 
|---|
| AWM Compliance | C22.2#239, Type ACIC, C22.2#174, HLABCD, C22.2#0.3, Clause 4.31 Low Acid Test | 
|---|
| CEC / C(UL) Compliance | ACIC, HLABCD, ACIC | 
|---|
| European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) | 
|---|
| APAC Compliance | China RoHS II (GB/T 26572-2011) | 
|---|
History
| Update and Revision | Revision Number: 0.235    Revision Date: 12-20-2022 | 
|---|
Documentation
Product Bulletins
Catalogs
Standards
Compliance Documentation