UL Type TC (1277) PVC-Nylon/PVC, 3 Conductor 12AWG (7x20) Bare Copper, PVC-NYL Insulation E2 Color Code, Black PVC Outer Jacket, 600V TC-ER 150V NPLF 90C Dry/Wet SUN RES DIR BUR
Specifications
Specifications
Product Overview
Suitable Applications | Power and Control Applications up to 600V |
---|
Construction Details
Conductor
Element | Number of Element | Size | Stranding | Material |
---|
Conductor(s) | 3 | 12 | 7x20 | BC - Bare Copper |
Insulation
Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|
PVC/Nylon - Polyvinyl Chloride + Nylon | 0.022 in (0.56 mm) | 0.134 in (3.40 mm) | Black, Red, Blue |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter | Ripcord |
---|
PVC - Polyvinyl Chloride | 0.047 in (1.2 mm) | 0.382 in (9.70 mm) | Yes |
Electrical Characteristics
Electricals
Nom. Conductor DCR | Max. Current |
---|
1.68 Ohm/1000ft | 30 Amps per Conductor at 30ºC |
Voltage
UL Voltage Rating |
---|
600 V (TC-ER), 150 V (NPLF) |
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|
90°C Dry, 90°C Wet | Wet/Dry: -30°C to 90°C |
Bend Radius
Stationary Min. | Installation Min. |
---|
1.52 in (38.6 mm) | 1.9 in (48 mm) |
Max. Pull Tension | 260.4 lbs (118.1 kg) |
---|
Bulk Cable Weight | 103 lbs/1000ft |
---|
Standards and Compliance
Environmental Suitability | Indoor, Outdoor, Sunlight Resistance, Burial |
---|
Flammability / Reaction to Fire | UL 1685 UL loading, IEEE 1202 FT4 |
---|
NEC / UL Compliance | Article 336, Article 760, NPLF, TC-ER, THWN-2 Singles |
---|
European Directive Compliance | EU CE Mark, EU Directive 2011/65/EU (RoHS 2) |
---|
History
Update and Revision | Revision Number: 0.555 Revision Date: 04-28-2023 |
---|
Documentation
Catalogs
Tools
Compliance Documentation
Data Sheets