Description

UL Type TC (1277) PVCN/PVC, 3+G Conductor 12+12AWG (Class B) Bare Copper, PVC-NYL Insulation E2 Color Code, Black PVC Outer Jacket, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR

Specifications

Specifications

Put-Up TypeReel

Product Overview

Suitable ApplicationsPower and Control Applications up to 600V

Construction Details

Conductor

ElementNumber of ElementSizeStrandingMaterial
Conductor(s)312 AWG7x20BC - Bare Copper
Ground Wire112 AWG7x20BC - Bare Copper

Insulation

ElementMaterialNom. ThicknessNom. Insulation DiameterColor Code
Conductor(s)PVC/Nylon - Polyvinyl Chloride + Nylon0.021 in (0.53 mm)0.134 in mmBlack, Red, Blue
Ground WirePVC/Nylon - Polyvinyl Chloride + Nylon0.017 in (0.43 mm)0.134 in inGreen

Outer Shield

Material
No Shield

Outer Jacket

MaterialNom. ThicknessNom. DiameterRipcord
PVC - Polyvinyl Chloride0.047 in (1.2 mm)0.417 in (10.6 mm)Yes
Overall Cable Diameter (Nominal)0.417 in (10.6 mm)

Electrical Characteristics

Electricals

ElementNom. Conductor DCRMax. Current
Conductor(s)1.72 Ohm/1000ft30 Amps per Conductor at 30ºC
Ground Wire1.72 Ohm/1000ft (5.64 Ohm/km)30 Amps per Conductor at 30ºC

Voltage

UL Voltage Rating
600 V (TC-ER), 150 V (NPLF)

Mechanical Characteristics

Temperature

UL TemperatureOperating
90°C Dry, 90°C Wet-25°C To +90°C

Bend Radius

Stationary Min.Installation Min.
1.668 in (42.37 mm)2.085 in (52.96 mm)
Max. Pull Tension347.2 lbs (157.5 kg)
Bulk Cable Weight131 lbs/1000ft

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, UV Resistance, Burial
Flammability / Reaction to FireUL 1685 UL Loading, IEEE 1202 FT4
NEC / UL ComplianceArticle 336, Article 760, Article 310, TC-ER, NPLF, THWN-2
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)

History

Update and RevisionRevision Number: 0.71 Revision Date: 04-14-2023