UL Type TC (1277) PVC-Nylon/PVC, 4 Conductor 12AWG (7x20) Bare Copper, PVC-NYL Insulation E2 Color Code, Black PVC Outer Jacket, 600V TC-ER 150V NPLF 90C Dry/Wet SUN RES DIR BUR
Specifications
Specifications
Product Overview
| Suitable Applications | Power and Control Applications up to 600V |
|---|
Construction Details
Conductor
| Element | Number of Element | Size | Stranding | Material |
|---|
| Conductor(s) | 4 | 12 | 7x20 | BC - Bare Copper |
Insulation
| Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
|---|
| PVC/Nylon - Polyvinyl Chloride + Nylon | 0.022 in (0.56 mm) | 0.123 in (3.12 mm) | Black, Red, Blue, Orange |
Outer Jacket
| Material | Nom. Thickness | Nom. Diameter | Ripcord |
|---|
| PVC - Polyvinyl Chloride | 0.047 in (1.2 mm) | 0.417 in (10.6 mm) | Yes |
Electrical Characteristics
Electricals
| Nom. Conductor DCR | Max. Current |
|---|
| 1.68 Ohm/1000ft | 24 Amps per Conductor at 30ºC |
Voltage
| UL Voltage Rating |
|---|
| 600 V (TC-ER), 150 V (NPLF) |
Mechanical Characteristics
Temperature
| UL Temperature | Operating |
|---|
| 90°C Dry, 90°C Wet | Wet/Dry: -30°C to 90°C |
Bend Radius
| Stationary Min. | Installation Min. |
|---|
| 1.64 in (41.7 mm) | 2.05 in (52.1 mm) |
| Max. Pull Tension | 347.2 lbs (157.5 kg) |
|---|
| Bulk Cable Weight | 132 lbs/1000ft |
|---|
Standards and Compliance
| Environmental Suitability | Indoor, Outdoor, Sunlight Resistance, Burial |
|---|
| Flammability / Reaction to Fire | UL 1685 UL loading, IEEE 1202 FT4 |
|---|
| CPR Compliance | CPR Euroclass: Eca |
|---|
| NEC / UL Compliance | Article 336, Article 760, NPLF, TC-ER, THWN-2 Singles |
|---|
| European Directive Compliance | EU CE Mark, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
|---|
| UK Regulation Compliance | UKCA Mark |
|---|
History
| Update and Revision | Revision Number: 0.539 Revision Date: 04-14-2023 |
|---|
Documentation
Catalogs
Tools
Compliance Documentation
Data Sheets