UL Type TC (1277) PVC-Nylon/PVC, 3+G Conductor 2/0+6AWG (Class B) Bare Copper, PVC-NYL Insulation M4 Color Code, Black PVC Outer Jacket, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR
Specifications
Specifications
Product Overview
Suitable Applications | Power and Control Applications up to 600V |
---|
Construction Details
Conductor
Element | Number of Element | Size | Stranding | Material |
---|
Conductor(s) | 3 | 2/0 | 19x11 | BC - Bare Copper |
Ground | 1 | 6 | 7x14 | BC - Bare Copper |
Insulation
Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|
PVC/Nylon - Polyvinyl Chloride + Nylon | 0.053 in (1.3 mm) | 0.508 in (12.9 mm) | Black and Numbered |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter | Ripcord |
---|
PVC - Polyvinyl Chloride | 0.083 in (2.1 mm) | 1.315 in (33.40 mm) | Yes |
Electrical Characteristics
Electricals
Element | Nom. Conductor DCR | Max. Current |
---|
Conductor(s) | 0.084 Ohm/1000ft | 195 Amps per Conductor at 30ºC |
Ground | 0.4 Ohm/1000ft (1.3 Ohm/km) | 75 Amps per Conductor at 30ºC |
Voltage
UL Voltage Rating |
---|
600 V (TC-ER) |
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|
90°C Dry, 90°C Wet | Wet/Dry: -30°C to 90°C |
Bend Radius
Stationary Min. | Installation Min. |
---|
6.55 in (166 mm) | 6.55 in (166 mm) |
Max. Pull Tension | 6025.1 lbs (2732.9 kg) |
---|
Bulk Cable Weight | 1666 lbs/1000ft |
---|
Standards and Compliance
Environmental Suitability | Indoor, Outdoor, Sunlight Resistance, Burial |
---|
Flammability / Reaction to Fire | UL 1685 UL loading, IEEE 1202 FT4 |
---|
NEC / UL Compliance | Article 336, TC-ER, THWN-2 |
---|
European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
---|
History
Update and Revision | Revision Number: 0.78 Revision Date: 04-28-2023 |
---|
Documentation
Catalogs
Tools
Compliance Documentation
Data Sheets