UL Type TC (1277) PVC-Nylon/PVC, 3+G Conductor 3/0+4AWG (Class B) Bare Copper, PVC-NYL Insulation M4 Color Code, Black PVC Outer Jacket, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR
Specifications
Specifications
Product Overview
| Suitable Applications | Power and Control Applications up to 600V |
|---|
Construction Details
Conductor
| Element | Number of Element | Size | Stranding | Material |
|---|
| Conductor(s) | 3 | 3/0 | 19x10 | BC - Bare Copper |
| Ground | 1 | 4 | 7x12 | BC - Bare Copper |
Insulation
| Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
|---|
| PVC/Nylon - Polyvinyl Chloride + Nylon | 0.055 in (1.4 mm) | 0.566 in (14.4 mm) | Black and Numbered |
Outer Jacket
| Material | Nom. Thickness | Nom. Diameter | Ripcord |
|---|
| PVC - Polyvinyl Chloride | 0.083 in (2.1 mm) | 1.425 in (36.20 mm) | Yes |
Electrical Characteristics
Electricals
| Element | Nom. Conductor DCR | Max. Current |
|---|
| Conductor(s) | 0.067 Ohm/1000ft | 225 Amps per Conductor at 30ºC |
| Ground | 0.26 Ohm/1000ft (0.85 Ohm/km) | 95 Amps per Conductor at 30ºC |
Voltage
| UL Voltage Rating |
|---|
| 600 V (TC-ER) |
Mechanical Characteristics
Temperature
| UL Temperature | Operating |
|---|
| 90°C Dry, 90°C Wet | Wet/Dry: -30°C to 90°C |
Bend Radius
| Stationary Min. | Installation Min. |
|---|
| 7.1 in (180 mm) | 7.1 in (180 mm) |
| Max. Pull Tension | 6463.6 lbs (2931.8 kg) |
|---|
| Bulk Cable Weight | 2034 lbs/1000ft |
|---|
Standards and Compliance
| Environmental Suitability | Indoor, Outdoor, Sunlight Resistance, Burial |
|---|
| Flammability / Reaction to Fire | UL 1685 UL loading, IEEE 1202 FT4 |
|---|
| NEC / UL Compliance | Article 336, TC-ER, THWN-2 |
|---|
| European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
|---|
History
| Update and Revision | Revision Number: 0.174 Revision Date: 04-28-2023 |
|---|
Documentation
Catalogs
Tools
Compliance Documentation
Data Sheets