UL Type TC (1277) PVC-Nylon/PVC, 4+G Conductor 4/0+4AWG (19x10+7x12) Bare Copper, PVC-NYL Insulation M4 Color Code, Black PVC Outer Jacket, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR
Specifications
Specifications
Product Overview
Suitable Applications | Power and Control Applications up to 600V |
---|
Construction Details
Conductor
Element | Number of Element | Size | Stranding | Material |
---|
Conductor(s) | 4 | 4/0 | 19x10 | BC - Bare Copper |
Ground | 1 | 4 | 7x12 | BC - Bare Copper |
Insulation
Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|
PVC/Nylon - Polyvinyl Chloride + Nylon | 0.054 in (1.4 mm) | 0.621 in (15.8 mm) | ICEA Chart M4 |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter | Ripcord |
---|
PVC - Polyvinyl Chloride | 0.116 in (2.95 mm) | 1.775 in (45.09 mm) | Yes |
Electrical Characteristics
Electricals
Element | Nom. Conductor DCR | Max. Current |
---|
Conductor(s) | 0.052 Ohm/1000ft | 208 Amps per Conductor at 30ºC |
Ground | 0.26 Ohm/1000ft (0.85 Ohm/km) | 95 Amps per Conductor at 30ºC |
Voltage
UL Voltage Rating |
---|
600 V (TC-ER) |
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|
90°C Dry, 90°C Wet | -30°C to 90°C Dry/Wet |
Bend Radius
Stationary Min. | Installation Min. |
---|
8.85 in (225 mm) | 8.85 in (225 mm) |
Max. Pull Tension | 10691 lbs (4849.4 kg) |
---|
Bulk Cable Weight | 3386 lbs/1000ft |
---|
Standards and Compliance
Environmental Suitability | Indoor, Outdoor, Sunlight Resistance, Burial |
---|
Flammability / Reaction to Fire | UL 1685 UL loading, IEEE 1202 FT4 |
---|
NEC / UL Compliance | Article 336, TC-ER, THWN-2 |
---|
European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
---|
APAC Compliance | China RoHS II (GB/T 26572-2011) |
---|
History
Update and Revision | Revision Number: 0.186 Revision Date: 04-28-2023 |
---|
Documentation
Catalogs
Tools
Compliance Documentation
Data Sheets