Description

UL Type TC (1277) PVC-Nylon/PVC, 37 Conductor 14AWG (Class B) Bare Copper, PVC-NYL Insulation E2 Color Code, Overall Beldfoil® Shield, Black PVC Outer Jacket, 600V TC-ER 150V NPLF 90C Dry/Wet SUN RES DIR BUR

Specifications

Specifications

Put-Up TypeReel

Product Overview

Suitable ApplicationsPower and Control Applications up to 600V

Construction Details

Conductor

ElementNumber of ElementSizeStrandingMaterial
Conductor(s)3714 AWG7x22BC - Bare Copper

Insulation

ElementMaterialNom. ThicknessNom. Insulation DiameterColor Code
Conductor(s)PVC/Nylon - Polyvinyl Chloride + Nylon0.021 in (0.53 mm)0.116 in mmBlack, Red, Blue, Orange, Yellow, Brown, Red/Black, Blue/Black, Orange/Black, Yellow/Black, Brown/Black, Black/Red, Blue/Red, Orange/Red, Yellow/Red, Brown/Red, Black/Blue, Red/Blue, Orange/Blue, Yellow/Blue, Brown/Blue, Black/Orange, Red/Orange, Blue/Orange, Yellow/Orange, Brown/Orange, Black/Yellow, Red/Yellow, Blue/Yellow, Orange/Yellow, Brown/Yellow, Black/Brown, Red/Brown, Blue/Brown, Orange/Brown, Yellow/Brown

Outer Shield

Shield TypeMaterialCoverageDrainwire Type
TapeBi-Laminate (Alum+Poly)100%14 AWG (7x22) TC

Outer Jacket

MaterialNom. ThicknessNom. DiameterRipcord
PVC - Polyvinyl Chloride0.084 in (2.1 mm)0.983 inYes
Overall Cable Diameter (Nominal)0.983 in

Electrical Characteristics

Electricals

Nom. Conductor DCRMax. Current
2.52 Ohm/1000ft10 Amps per Conductor at 30ºC

Voltage

UL Voltage Rating
600 V (TC-ER), 150 V (NLPF)

Mechanical Characteristics

Temperature

UL TemperatureOperating
90°C Dry, 90°C WetWet/Dry: -30°C To +90°C

Bend Radius

Stationary Min.Installation Min.
11.796 in (299.62 mm)11.796 in
Max. Pull Tension2074.8 lbs (941.11 kg)
Bulk Cable Weight773 lbs/1000ft

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, UV Resistance, Burial
Flammability / Reaction to FireUL 1685 UL Loading, IEEE 1202 FT4
NEC / UL ComplianceArticle 336, NPLF, TC-ER, THWN-2
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.54 Revision Date: 06-07-2023