Canadian Instrumentation Cable TC-ACIC 600V, 4+G Conductor 18AWG (7x26) Bare Copper, XLPE Insulation, PVC Inner Jacket, Aluminum Interlock Armor, Blue PVC Outer Jacket, 90C Dry/Wet CSA HL SUN RES -40C
Specifications
Specifications
Product Overview
| Suitable Applications | Power and Control Applications up to 600V |
|---|
Construction Details
Conductor
| Element | Number of Element | Size | Stranding | Material |
|---|
| Conductor(s) | 4 | 18 AWG | 7x26 | BC - Bare Copper |
| Ground Wire | 1 | 18 AWG | 7x26 | BC - Bare Copper |
Insulation
| Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
|---|
| Conductor(s) | XLP, XLPO, XLPE (Thermoset) | 0.03 in (0.76 mm) | 0.106 in (2.69 mm) | White and Numbered 1, Black and Numbered 2, Black and Numbered 3, Black and Numbered 4 |
| Ground Wire | XLP, XLPO, XLPE (Thermoset) | 0.03 in (0.76 mm) | 0.106 in (2.69 mm) | Green |
Outer Shield
Inner Jacket
| Material | Nom. Thickness | Nom. Diameter | Ripcord | Color |
|---|
| PVC - Polyvinyl Chloride | 0.047 in (1.2 mm) | 0.385 in (9.78 mm) | Yes | Black |
| Table Notes | Separator - Corrugated Mylar Tape |
|---|
Armor
| Armor Type & Material | Armor Thickness | Diameter Over Armor |
|---|
| AIA - Aluminum Interlock Armor | 0.025 in (0.64 mm) | 0.610 in (15.5 mm) |
Outer Jacket
| Material | Nom. Thickness | Nom. Diameter | Ripcord |
|---|
| PVC - Polyvinyl Chloride | 0.052 in (1.3 mm) | 0.714 in | Yes |
| Overall Cable Diameter (Nominal) | 0.714 in |
|---|
Electrical Characteristics
Electricals
| Element | Nom. Conductor DCR | Max. Current |
|---|
| Conductor(s) | 6.9 Ohm/1000ft | 11.2 Amps per Conductor at 30ºC |
| Ground Wire | 6.9 Ohm/1000ft (23 Ohm/km) | 14 Amps per Conductor at 30ºC |
Voltage
| Voltage Rating |
|---|
| 600 V (CSA TC) |
Mechanical Characteristics
Temperature
Bend Radius
| Stationary Min. | Installation Min. |
|---|
| 8.56 in (217 mm) | 8.56 in |
| Max. Pull Tension | 312 lbs (142 kg) |
|---|
| Bulk Cable Weight | 206 lbs/1000ft |
|---|
Standards and Compliance
| Environmental Suitability | Indoor, Outdoor, Sunlight Resistance, UV Resistance |
|---|
| CEC / C(UL) Compliance | CSA ACIC |
|---|
| European Directive Compliance | EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
|---|
| APAC Compliance | China RoHS II (GB/T 26572-2011) |
|---|
History
| Update and Revision | Revision Number: 0.208 Revision Date: 12-20-2022 |
|---|
Documentation
Catalogs
Tools
Compliance Documentation
Data Sheets