Belden Basics VFD, 3 Conductor 14AWG (7x22) Bare Copper XLPE Insulation M4 Color Code + 14AWG Symmetrical Segmented Ground (3 of 18AWG) Bare Copper Stranded, Overall Dual Copper Tapes Helically Applied Shield, Black PVC Outer Jacket, 600/1000V TC-ER 90C Dry/Wet 1000V CSA AWM I/II A/B SUN RES DIR BUR Oil Resistant
Specifications
Specifications
Product Overview
Suitable Applications | Variable Frequency Drives (VFD); AC Motor and Drive Systems |
---|
Construction Details
Conductor
Element | Number of Element | Size | Stranding | Material | Notes |
---|
Conductor(s) | 3 | 14 AWG | 7x22 | BC - Bare Copper | |
Ground Wire | 3 | 18 AWG | 7x26 | BC - Bare Copper | Segmented Grounds |
Insulation
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|
Conductor(s) | XLPE - Cross-Linked Polyethylene (Thermoset) | 0.030 in (0.76 mm) | 0.131 in (3.33 mm) | ICEA Chart M4 |
Ground Wire | No Insulation | | | |
Outer Shield
Shield Type | Material | Coverage |
---|
Helical Tape | Bare Copper (BC) | 100% |
Helical Tape | Bare Copper (BC) | 100% |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter | Ripcord |
---|
PVC - Polyvinyl Chloride | 0.060 in (1.5 mm) | 0.425 in (10.8 mm) | Yes |
Overall Cable Diameter (Nominal) | 0.425 in (10.8 mm) |
---|
Electrical Characteristics
Electricals
Element | Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Nom. Capacitance Cond-to-Other (Conds + Shield) | Nom. Characteristic Impedence | Nom. Velocity of Prop. | Max. Current |
---|
Conductor(s) | 2.282 Ohm/1000ft | 23 pF/ft (75 pF/m) | 42 pF/ft (140 pF/m) | 80 Ohm | 55% | 25 Amps per Conductor at 30ºC |
| 7.06 Ohm/1000ft (23.2 Ohm/km) | | | | | 25 Amps per Conductor at 25ºC |
Voltage
UL Voltage Rating |
---|
600 / 1000 V (TC-ER) |
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|
90°C Dry, 90°C Wet | -40°C To +90°C |
Bend Radius
Stationary Min. | Installation Min. |
---|
5.1 in (130 mm) | 5.1 in (130 mm) |
Max. Pull Tension | 186 lbs (84.4 kg) |
---|
Bulk Cable Weight | 134 lbs/1000ft |
---|
Standards and Compliance
Environmental Suitability | Indoor, Outdoor, Sunlight Resistance, Burial |
---|
Sustainability | CA Prop 65 |
---|
Flammability / Reaction to Fire | UL 1685 UL Loading, IEEE 1202 FT4 |
---|
NEC / UL Compliance | Article 336, TC-ER, XHHW-2 |
---|
ICEA Compliance | S-95-658 |
---|
European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
---|
APAC Compliance | China RoHS II (GB/T 26572-2011) |
---|
History
Update and Revision | Revision Number: 0.571 Revision Date: 04-14-2023 |
---|