Belden 100% Ground Flexible VFD, 3 Conductor 2/0AWG (7x19x20) Tinned Copper XLPE Insulation M4 Color Code + 2/0AWG Symmetrical Segmented Ground (3 of 4AWG+) Bare Copper Stranded, Overall Dual Copper Tapes Helically Applied Shield, Black PVC Outer Jacket, 600V TC-ER 90C Dry/Wet 1000V Flexible Motor Supply Cable WTTC 1000V CSA AWM I/II A/B 600V RW90 TC SUN RES DIR BUR Oil Resistant
Specifications
Specifications
Product Overview
Suitable Applications | Variable Frequency Drives (VFD); AC Motor and Drive Systems |
---|
Construction Details
Conductor
Element | Number of Element | Size | Stranding | Material | Notes |
---|
Conductor(s) | 3 | 2/0 AWG | 7x19x20 | TC - Tinned Copper | |
Ground Wire | 3 | 4 AWG | 7x19x25 | BC - Bare Copper | Segmented Grounds |
Insulation
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|
Conductor(s) | XLPE - Cross-Linked Polyethylene (Thermoset) | 0.057 in (1.4 mm) | 0.552 in (14.0 mm) | ICEA Chart M4 |
Ground Wire | No Insulation | | | |
Outer Shield
Shield Type | Material | Coverage |
---|
Helical Tape | Bare Copper (BC) | 100% |
Helical Tape | Bare Copper (BC) | 100% |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter | Ripcord |
---|
PVC - Polyvinyl Chloride | 0.083 in (2.1 mm) | 1.368 in (34.75 mm) | Yes |
Overall Cable Diameter (Nominal) | 1.368 in (34.75 mm) |
---|
Electrical Characteristics
Electricals
Element | Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Nom. Capacitance Cond-to-Other (Conds + Shield) | Nom. Characteristic Impedence | Nom. Velocity of Prop. | Max. Current |
---|
Conductor(s) | 0.075 Ohm/1000ft | 50 pF/ft (160 pF/m) | 90 pF/ft (300 pF/m) | 36 Ohm | 55% | 195 Amps per Conductor at 30ºC |
| 0.27 Ohm/1000ft (0.89 Ohm/km) | | | | | 95 Amps per Conductor at 25ºC |
Voltage
UL Voltage Rating |
---|
1000 V (TC, WTTC, UL44, UL Flexible Motor Supply Cable), 600 V (C(UL) CIC TC) |
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|
90°C Dry, 90°C Wet | -40°C To +90°C |
Bend Radius
Stationary Min. | Installation Min. |
---|
16.4 in (417 mm) | 16.4 in (417 mm) |
Max. Pull Tension | 6607 lbs (2997 kg) |
---|
Bulk Cable Weight | 2016 lbs/1000ft |
---|
Standards and Compliance
Environmental Suitability | Indoor, Outdoor, Sunlight Resistance, Burial |
---|
Sustainability | CA Prop 65 |
---|
Flammability / Reaction to Fire | UL 1685 UL Loading, FT4, IEEE 1202 FT4 |
---|
NEC / UL Compliance | Article 336, TC-ER, WTTC, XHHW-2, UL Flexible Motor Supply Cable |
---|
CEC / C(UL) Compliance | TC |
---|
ICEA Compliance | S-95-658 |
---|
European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
---|
APAC Compliance | China RoHS II (GB/T 26572-2011) |
---|
Other Standard Compliance(s) | P-07-KA070003-MSHA |
---|
History
Update and Revision | Revision Number: 0.584 Revision Date: 04-28-2023 |
---|