Belden 100% Ground Flexible VFD, 3 Conductor 1/0AWG (7x19x21) Tinned Copper XLPE Insulation M4 Color Code + 1/0AWG Symmetrical Segmented Ground (3 of 4AWG) Bare Copper Stranded, Overall Dual Copper Tapes Helically Applied Shield, Black PVC Outer Jacket, 2000V TC-ER 90C Dry/Wet 2000V Flexible Motor Supply Cable WTTC 1000V CSA AWM I/II A/B 2000V RW90 TC SUN RES DIR BUR Oil Resistant
Specifications
Specifications
Product Overview
| Suitable Applications | Variable Frequency Drives (VFD); AC Motor and Drive Systems; High voltage requirements |
|---|
Construction Details
Conductor
| Element | Number of Element | Size | Stranding | Material | Notes |
|---|
| Conductor(s) | 3 | 1/0 AWG | 7x19x21 | TC - Tinned Copper | |
| Ground | 3 | 4 AWG | 7x19x25 | BC - Bare Copper | Segmented Grounds |
Insulation
| Element | Material | Nom. Thickness | Color Code |
|---|
| Conductor(s) | XLPE - Cross-Linked Polyethylene (Thermoset) | 0.093 in (2.4 mm) | Black and Numbered |
| Ground | No Insulation | | |
Outer Shield
| Shield Type | Material | Coverage |
|---|
| Helical Tape | Bare Copper (BC) | 100% |
| Helical Tape | Bare Copper (BC) | 100% |
Outer Jacket
| Material | Nom. Thickness | Nom. Diameter | Ripcord |
|---|
| PVC - Polyvinyl Chloride | 0.083 in (2.1 mm) | 1.447 in (36.75 mm) | Yes |
| Overall Cable Diameter (Nominal) | 1.447 in (36.75 mm) |
|---|
Electrical Characteristics
Electricals
| Element | Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Nom. Capacitance Cond-to-Other (Conds + Shield) | Nom. Characteristic Impedence | Nom. Velocity of Prop. | Max. Current |
|---|
| Conductor(s) | 0.094 Ohm/1000ft (0.31 Ohm/km) | 50 pF/ft (160 pF/m) | 90 pF/ft (300 pF/m) | 36 Ohm | 55% | 170 Amps per Conductor at 30ºC |
Voltage
| UL Voltage Rating |
|---|
| 2000 V (TC, C(UL) TC), 1000 V (WTTC, UL Flexible Motor Supply Cable, CSA AWM I/II A/B) |
Mechanical Characteristics
Temperature
| UL Temperature | Operating |
|---|
| 90°C Dry, 90°C Wet | -40°C To +90°C |
Bend Radius
| Stationary Min. | Installation Min. |
|---|
| 17.4 in (442 mm) | 17.4 in (442 mm) |
| Max. Pull Tension | 4737 lbs (2149 kg) |
|---|
| Bulk Cable Weight | 1905 lbs/1000ft (2835 kg/km) |
|---|
Standards and Compliance
| Environmental Suitability | Indoor, Outdoor, Sunlight Resistance, Oil Resistance, Burial |
|---|
| Sustainability | CA Prop 65 |
|---|
| Flammability / Reaction to Fire | UL1685 UL Loading, FT4, 1202, 383 Vertical Tray Flame Test (70,000 BTU) |
|---|
| NEC / UL Compliance | Article 336, TC-ER, WTTC, RHW-2, UL Flexible Motor Supply Cable |
|---|
| AWM Compliance | I/II A/B |
|---|
| CEC / C(UL) Compliance | TC |
|---|
| ICEA Compliance | S-95-658 |
|---|
| European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
|---|
| APAC Compliance | China RoHS II (GB/T 26572-2011) |
|---|
History
| Update and Revision | Revision Number: 0.486 Revision Date: 04-14-2023 |
|---|