Belden Basics CSA VFD, 3 Conductor 14AWG (7x22) Bare Copper XLPE Insulation M4 Color Code + 14AWG Symmetrical Segmented Ground (3 of 18AWG) Bare Copper Stranded, Overall Dual Copper Tapes Helically Applied Shield, Black PVC Outer Jacket, 1000V CSA TC C22.2 #230 C22.2 #38 SUN RES DIR BUR Oil Resistance
Specifications
Specifications
Product Overview
Suitable Applications | Variable Frequency Drives (VFD); AC Motor and Drive Systems; Specific ratings for applications in Canada |
---|
Construction Details
Conductor
Element | Number of Element | Size | Stranding | Material | Notes |
---|
Conductor(s) | 3 | 14 AWG | 7x22 | BC - Bare Copper | |
Ground | 3 | 18 AWG | 7x26 | BC - Bare Copper | Segmented Grounds |
Insulation
Element | Material | Nom. Thickness | Color Code |
---|
Conductor(s) | XLPE - Cross-Linked Polyethylene (Thermoset) | 0.045 in (1.1 mm) | Black and Numbered |
Ground | No Insulation | | |
Outer Shield
Shield Type | Material | Coverage |
---|
Helical Tape | Bare Copper (BC) | 100% |
Helical Tape | Bare Copper (BC) | 100% |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter | Ripcord |
---|
PVC - Polyvinyl Chloride | 0.058 in (1.5 mm) | 0.494 in (12.5 mm) | Yes |
Overall Cable Diameter (Nominal) | 0.494 in (12.5 mm) |
---|
Electrical Characteristics
Electricals
Element | Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Nom. Capacitance Cond-to-Other (Conds + Shield) | Nom. Characteristic Impedence | Nom. Velocity of Prop. | Max. Current |
---|
Conductor(s) | 2.267 Ohm/1000ft (7.438 Ohm/km) | 30 pF/ft (98 pF/m) | 54 pF/ft (180 pF/m) | 62 Ohm | 55% | 25 Amps per Conductor at 30ºC |
Voltage
UL Voltage Rating |
---|
1000 V (CSA TC) |
Mechanical Characteristics
Temperature
Bend Radius
Stationary Min. | Installation Min. |
---|
5.9 in (150 mm) | 5.9 in (150 mm) |
Max. Pull Tension | 231 lbs (105 kg) |
---|
Bulk Cable Weight | 160 lbs/1000ft (240 kg/km) |
---|
Standards and Compliance
Environmental Suitability | Indoor, Outdoor, Sunlight Resistance, Oil Resistance, Burial |
---|
Sustainability | CA Prop 65 |
---|
Flammability / Reaction to Fire | 1202, 383 Vertical Tray Flame Test (70,000 BTU) |
---|
CEC / C(UL) Compliance | TC, RW90, C22.2 #230, #38 |
---|
ICEA Compliance | S-95-658 |
---|
European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
---|
APAC Compliance | China RoHS II (GB/T 26572-2011) |
---|
History
Update and Revision | Revision Number: 0.348 Revision Date: 12-20-2022 |
---|