Belden

3051A - Inst, 16 Pr #16+22 Str BC, PVC Ins E1, IS/OS, Blk PVC Jkt, 300V PLTC ITC CMG

(No reviews yet) Write a Review
SKU:
3051A
Shipping:
Calculated at Checkout
$0.00

Description

UL Instrumentation, 16 Pair 16+22AWG (7x24+7x30) Bare Copper, PVC Insulation E1 Color Code, Individual & Overall Beldfoil® Shield, Black PVC Outer Jacket, PLTC ITC CMG AWM 2464 SUN RES DIR BUR

Specifications

Specifications

Product Overview

Suitable ApplicationsIndustrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, ...),low voltage digital control (24v, …), encoders, control circuits, distributed control system (DCS),programmable logic controller (PLC), Solenoids, Valves, Actuators, Positioners

Construction Details

Conductor

ElementNumber of ElementSizeStrandingMaterial
Pair(s)1616 AWG7x24BC - Bare Copper
Comm Wire(s)122 AWG7x30BC - Bare Copper

Insulation

ElementMaterialNom. ThicknessColor Code
Pair(s)PVC - Polyvinyl Chloride0.017 in (0.43 mm)Black, White and Numbered
Comm Wire(s)PVC - Polyvinyl Chloride0.019 in (0.48 mm)Orange

Inner Shield

ElementShield TypeMaterialCoverageDrainwire Type
Pair(s)TapeBi-Laminate (Alum+Poly)100%18 AWG (7x26) TC
Comm Wire(s)No Shield

Outer Shield

Shield TypeMaterialCoverageDrainwire Type
TapeBi-Laminate (Alum+Poly)100%16 AWG (7x24) TC

Outer Jacket

MaterialNom. ThicknessNom. DiameterRipcord
PVC - Polyvinyl Chloride0.073 in (1.9 mm)0.908 in (23.1 mm)Yes
Overall Cable Diameter (Nominal)0.908 in (23.1 mm)

Electrical Characteristics

Electricals

ElementNom. Conductor DCRNom. Capacitance Cond-to-Other (Conds + Shield)
Pair(s)4.2 Ohm/1000ft (14 Ohm/km)110 pF/ft (360 pF/m)
Comm Wire(s)14.7 Ohm/1000ft (48.2 Ohm/km)

Voltage

UL Voltage Rating
300 V (PLTC, CMG, UL AWM 2464), 150 V (ITC)

Mechanical Characteristics

Temperature

UL TemperatureOperating
105°C-30°C to +105°C

Bend Radius

Stationary Min.Installation Min.
9.1 in (230 mm)9.1 in (230 mm)
Max. Pull Tension661 lbs (300 kg)
Bulk Cable Weight573 lbs/1000ft

Standards and Compliance

Environmental SuitabilityIndoor/Outdoor, Indoor, Outdoor, Sunlight Resistance, Burial
Flammability / Reaction to FireUL1685 (FT4 Loading), FT4, 1202
NEC / UL ComplianceArticle 725, Article 727, Article 800, CMG, ITC, PLTC
AWM ComplianceAWM 2464
CEC / C(UL) ComplianceCMG
European Directive ComplianceEU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.206 Revision Date: 04-14-2023
View AllClose