Belden

3076T - Fieldbus, 1 Pr #18 Str TC, PP Ins, OS, LSZH Jkt, CMG ISA/SP-50 Type A, PLTC-ER, ITC-ER, CMG

(No reviews yet) Write a Review
SKU:
3076T
Shipping:
Calculated at Checkout
$0.00

Description

Fieldbus, 1 Pair 18AWG (7x26) Tinned Copper, PP Insulation, Overall Beldfoil® Shield, LSZH Outer Jacket, CMG ISA/SP-50 Type A, PLTC-ER, ITC-ER, CMG

Specifications

Specifications

Product Overview

Suitable Applicationsharsh environment digital and serial two-way communication, oil and gas extraction and refining sites, petrochemical, Profibus process automation or Foundation FieldBus process automation, extreme temperature environments, exposure to humidity/moisture, dust, and oil, remote locations long distance applications, etc.

Construction Details

Conductor

ElementNumber of ElementSizeStrandingMaterial
Pair(s)118 AWG7x26TC - Tinned Copper

Insulation

ElementMaterialNom. ThicknessColor Code
Pair(s)PP - Polypropylene0.022 in (0.56 mm)Blue & Orange

Outer Shield

Shield TypeMaterialCoverageDrainwire Type
TapeBi-Laminate (Alum+Poly)100%20 AWG (7x28) TC

Outer Jacket

MaterialNom. ThicknessNom. Diameter
LSZH - Low Smoke Zero Halogen (Flame Retardant)0.100 in (2.54 mm)0.380 in (9.65 mm)
Overall Cable Diameter (Nominal)0.380 in (9.65 mm)

Electrical Characteristics

Electricals

ElementNom. Conductor DCRNom. Capacitance Cond-to-Other (Conds + Shield)Nom. Characteristic ImpedenceNom. Velocity of Prop.Max. Current
Pair(s)5.86 Ohm/1000ft (19.2 Ohm/km)45.0 pF/ft100 Ohm66%5.2 Amps per Conductor
Nom. Outer Shield DCR7.5 Ohm/1000ft (25 Ohm/km)

High Frequency (Nominal/Typical)

ElementFrequency [MHz]Nom. Insertion Loss (Attenuation)
Pair(s)0.0390.091 dB/100ft

Voltage

UL Voltage Rating
300 V (CMG, PLTC-ER), 150 V (ITC-ER)

Mechanical Characteristics

Temperature

UL TemperatureOperating
105°C-20°C to +105°C
Max. Pull Tension60 lbs (27 kg)
Bulk Cable Weight77 lbs/1000ft (110 kg/km)

Standards and Compliance

Environmental SuitabilityBurial
Flammability / Reaction to FireUL 1685 UL Loading, FT4, 1202, IEC 60332-3-22
NEC / UL ComplianceArticle 725, Article 727, Article 800, CMG, ITC-ER, PLTC-ER
CEC / C(UL) ComplianceCMG
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.320 Revision Date: 05-05-2023
View AllClose

Additional Information

Variant_Options:
Item #|Color|UPC
Variant_Options 3076T 0105000:
3076T 0105000|Black|612825140276
View AllClose