DeviceBus® for Honeywell SDS, 2 Pair 16+20AWG (19x28+19x32) Tinned Copper, PVC+Foam PE Insulation, Individual Beldfoil® Shield, PVC Outer Jacket, CL2
Specifications
Specifications
Product Overview
Suitable Applications | harsh environment, IIoT, factory or process automation, video, audio, data communication, etc. |
---|
Construction Details
Conductor
Element | Number of Element | Size | Stranding | Material |
---|
Power Pair(s) | 1 | 16 AWG | 19x28 | TC - Tinned Copper |
Data Pair(s) | 1 | 20 AWG | 19x32 | TC - Tinned Copper |
Insulation
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|
Power Pair(s) | PVC - Polyvinyl Chloride | 0.016 in (0.41 mm) | 0.090 in (2.3 mm) | Blue & Brown |
Data Pair(s) | PE - Polyethylene (Foam) | 0.042 in (1.1 mm) | 0.120 in (3.05 mm) | Black & White |
Inner Shield
Element | Shield Type | Material | Coverage | Drainwire Type | Notes |
---|
Power Pair(s) | Tape | Bi-Laminate (Alum+Poly) | 100% | | |
Data Pair(s) | Tape | Bi-Laminate (Alum+Poly) | 100% | 20 AWG (19x32) TC | Power & Data Pairs share same Drainwire |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter |
---|
PVC - Polyvinyl Chloride | 0.040 in (1.0 mm) | 0.398 in (10.1 mm) |
Overall Cable Diameter (Nominal) | 0.398 in (10.1 mm) |
---|
Electrical Characteristics
Electricals
Element | Nom. Conductor DCR | Nom. Inner Shield DCR | Nom. Capacitance Cond-to-Cond | Nom. Characteristic Impedence | Nom. Velocity of Prop. | Max. Current |
---|
Power Pair(s) | 4.52 Ohm/1000ft | 6.94 Ohm/1000ft (22.8 Ohm/km) | | | | 18 Amps per Conductor at 30ºC |
Data Pair(s) | 11.3 Ohm/1000ft (37.1 Ohm/km) | 5.75 Ohm/1000ft (18.9 Ohm/km) | 12 pF/ft (39 pF/m) | 120 Ohm | 76% | 8 Amps per Conductor at 30ºC |
High Frequency (Nominal/Typical)
Element | Frequency [MHz] | Nom. Insertion Loss (Attenuation) |
---|
Data Pair(s) | 0.125 | 0.18 dB/100ft |
| 0.5 | 0.35 dB/100ft |
| 1 | 0.47 dB/100ft |
High Frequency
Max./Min. Input Impedance (unFitted) [Ohm] |
---|
120 |
Voltage
UL Voltage Rating | Voltage Rating |
---|
300 V (CL2), 300 V (AWM 2464) | 300 V (AWM I/II A) |
Mechanical Characteristics
Temperature
UL Temperature | Operating | Storage |
---|
80°C | -20°C to +80°C | -40°C to +80 °C |
Bend Radius
Stationary Min. | Installation Min. |
---|
3.98 in (101 mm) | 3.98 in (101 mm) |
Max. Pull Tension | 125 lbs (56.7 kg) |
---|
Bulk Cable Weight | 79 lbs/1000ft |
---|
Standards and Compliance
Environmental Suitability | Indoor |
---|
Flammability / Reaction to Fire | UL 1685 UL Loading, IEC 60332-1-2 |
---|
CPR Compliance | CPR Euroclass: Eca |
---|
NEC / UL Compliance | Article 725, CL2 |
---|
AWM Compliance | AWM 2464, AWM I/II A |
---|
European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
---|
UK Regulation Compliance | UKCA Mark |
---|
APAC Compliance | China RoHS II (GB/T 26572-2011) |
---|
Product Notes
History
Update and Revision | Revision Number: 0.476 Revision Date: 01-20-2023 |
---|
Documentation
Product Bulletins
Catalogs
Brochures
Compliance Documentation
Data Sheets