ControlBus™, Coax RG11 14AWG (Solid) Bare Copper Covered Steel, FEP Insulation, Overall Duofoil®+ Aluminum Braid(60%)+Overall Duofoil®+Aluminum Braid(40%) Shield, PVDF Outer Jacket, CMP
Specifications
Specifications
Product Overview
Suitable Applications | harsh environment, factory automation, ControlNet™, Modbus II, Industrial Coax, Belden ControlNet cables provide maximum signal integrity and run length exceeding the high-speed, time-critical requirements necessary for ControlNet factory floor applications |
---|
Physical Characteristics (Overall)
Conductor
AWG | Stranding | Material | Nominal Diameter | No. of Coax |
---|
14 | Solid | BCCS - Bare Copper Covered Steel | 0.064 in | 1 |
Insulation
Material | Nominal Diameter |
---|
FEP - Fluorinated Ethylene Propylene (Foam) | 0.28 in |
Outer Shield
Type | Layer | Material | Material Trade Name | Coverage [%] |
---|
Tape | 1 | Tri-Laminate (Alum+Poly+Alum) | Duofoil® | 100% |
Braid | 2 | Aluminum | | 60% |
Tape | 3 | Tri-Laminate (Alum+Poly+Alum) | Duofoil® | 100% |
Braid | 4 | Aluminum | | 40% |
Outer Jacket
Material | Nominal Diameter |
---|
PVDF - Polyvinylidene Fluoride | 0.387 in |
Electrical Characteristics
Conductor DCR
Nominal Conductor DCR | Nominal Outer Shield DCR | Outer Conductor DCR |
---|
11 Ohm/1000ft | 3.9 Ohm/1000ft | 3.9 Ohm/1000ft |
Capacitance
Nom. Capacitance Conductor to Shield |
---|
16.5 pF/ft |
Inductance
Nominal Inductance |
---|
0.097 µH/ft |
Impedance
Nominal Characteristic Impedance | Nominal Characteristic Tolerance |
---|
100 Ohm | ± 3 Ohm |
High Frequency (Nominal/Typical)
Frequency [MHz] | Nom. Insertion Loss |
---|
1 MHz | 0.17 dB/100ft |
2 MHz | 0.22 dB/100ft |
5 MHz | 0.28 dB/100ft |
10 MHz | 0.4 dB/100ft |
20 MHz | 0.6 dB/100ft |
50 MHz | 1.2 dB/100ft |
100 MHz | 1.7 dB/100ft |
200 MHz | 2.5 dB/100ft |
300 MHz | 3.04 dB/100ft |
400 MHz | 3.5 dB/100ft |
Delay
Nominal Delay | Nominal Velocity of Propagation (VP) [%] |
---|
1.2 ns/ft | 82% |
Phase Delay Distortion
f/B | %PDD/100M (5MB) |
---|
0.5 | -0.6 |
1 | -0.46 |
1.5 | 0 |
2 | 0.17 |
2.5 | 0.3 |
High Frequency
Frequency [MHz] | Min. SRL (Structural Return Loss) |
---|
1 MHz | 20 dB |
2 MHz | |
5 MHz | |
10 MHz | |
20 MHz | |
50 MHz | |
100 MHz | |
200 MHz | |
300 MHz | |
400 MHz | |
Voltage
UL Voltage Rating |
---|
300 V RMS |
Electrical Characteristics Notes | Tilt 5 to 10 MHz: .42 dB/100 M |
---|
Other Electrical Characteristic 2 | Tilt 10 to 20 MHz: .58 dB/100 M |
---|
Other Electrical Characteristic 3 | SLR Min. 20dB (5MHz - 50MHz) |
---|
Temperature Range
UL Temp Rating | 150°C |
---|
Operating Temperature Range | -20°C To +150°C |
---|
Mechanical Characteristics
Bulk Cable Weight | 68 lbs/1000ft |
---|
Max. Pull Tension | 309 lbs |
---|
Min. Bend Radius/Minor Axis | 4 in |
---|
Standards
NEC Articles | Article 800 |
---|
NEC/(UL) Compliance | CMP |
---|
CEC/C(UL) Compliance | CMP |
---|
RG Type | 11 |
---|
Applicable Environmental and Other Programs
EU Directive 2000/53/EC (ELV) | Yes |
---|
EU Directive 2011/65/EU (RoHS 2) | Yes |
---|
EU Directive 2012/19/EU (WEEE) | Yes |
---|
EU Directive 2015/863/EU (RoHS 2 amendment) | Yes |
---|
EU Directive Compliance | EU Directive 2003/11/EC (BFR) |
---|
MII Order #39 (China RoHS) | Yes |
---|
Suitability
Suitability - Burial | Yes |
---|
Suitability - Outdoor | Yes |
---|
Flammability, LS0H, Toxicity Testing
UL Flammability | NFPA 262 |
---|
UL voltage rating | 300 V RMS |
---|
Plenum/Non-Plenum
Related Part Numbers
Product Notes
Notes | Sweep tested 5 to 400 MHz. Tap marks every 2.6 meters to aid users in installation. |
---|
History
Update and Revision | Revision Number: 0.303 Revision Date: 05-05-2023 |
---|
Documentation
Catalogs
Technical Resources
Data Sheets