RS-485, 2 Pair AWG 22 Tinned Copper - Stranded, Polyolefin (PO, PE, PP) insulation, Foil + Braid(s) shielding, LSZH / FRNC jacket ,SWA
Specifications
Specifications
Product Overview
| Suitable Applications | Instrumentation and computer cable. For EIA RS-485 transmissions applications |
|---|
Physical Characteristics (Overall)
Conductor
| AWG | Stranding | Material | No. of Pairs |
|---|
| 22 | 7x30 | TC - Tinned Copper | 2 |
| Conductor Count | 4 |
|---|
| Total Number of Pairs | 2 |
|---|
Insulation
| Material | Nominal Diameter | Diameter +/- Tolerance |
|---|
| PE - Polyethylene (Foam) | 2.04 mm | 0.05 mm |
Color Chart
| Number | Color |
|---|
| Pair 1 | White/Blue & Blue/White |
| Pair 2 | White/Orange & Orange/White |
Inner Shield
| Material | Material Trade Name | Drainwire Material |
|---|
| Bi-Laminate (Alum+Poly) | Beldfoil® | TC - Tinned Copper |
Inner Jacket
| Nominal Diameter | Nominal Wall Thickness |
|---|
| 8.9 mm | 1.35 mm |
Outer Shield
| Type | Layer | Material | Material Trade Name | Coverage [%] | Drainwire Material | Drainwire AWG |
|---|
| Tape | 1 | | Beldfoil® | 100% | TC - Tinned Copper | 22 |
| Braid | 2 | Tinned Copper (TC) | | 65% | | |
Outer Jacket
| Material | Color | Nominal Diameter | Nominal Wall Thickness |
|---|
| LSZH - Low Smoke Zero Halogen (Flame Retardant) | Black | 13.3 mm | 1.35 mm |
Construction and Dimensions
Armor
| Type of Armor | Material | Thickness of Armoring Wires | Coverage Percentage |
|---|
| Steel Wire Armoring | Galvanized steel wire | 0.9 mm | Min. 90% |
Electrical Characteristics
Conductor DCR
| Nominal Conductor DCR | Nominal Outer Shield DCR |
|---|
| 48.2 Ohm/km | 5.9 Ohm/km |
Capacitance
| Nom. Capacitance Conductor to Conductor | Nom. Capacitance Conductor to Other Conductor to Shield |
|---|
| 36.1 pF/m | 68.6 pF/m |
Impedance
| Frequency [MHz] | Nominal Characteristic Impedance |
|---|
| 1 MHz | 120 Ohm |
High Frequency (Nominal/Typical)
| Frequency [MHz] | Nom. Insertion Loss |
|---|
| 1 MHz | 1.64 dB/100m |
Delay
| Nominal Velocity of Propagation (VP) [%] |
|---|
| 78% |
Current
| Element | Max. Recommended Current [A] |
|---|
| Conductor(s) | 2.1 Amps per Conductor |
Voltage
Temperature Range
| Installation Temperature Range | -15°C To +80°C |
|---|
| Storage Temperature Range | -45°C To +80°C |
|---|
| Operating Temperature Range | -15°C To +80°C |
|---|
| Operating Temp Range (Fixed Install) | -45°C To +80°C |
|---|
Mechanical Characteristics
| Oil Resistance | IEC 60811-404 |
|---|
| Max. Pull Tension | 290 N |
|---|
| Min Bend Radius (W/o Pulling Strength) | 200 mm |
|---|
| Min. Bend Radius During Installation | 260 mm |
|---|
Standards
| CENELEC Compliance | EN 50290-2-20 |
|---|
Applicable Environmental and Other Programs
| Environmental Space | Indoor/Outdoor |
|---|
Suitability
| Suitability - Indoor | Yes |
|---|
| Suitability - Non-Halogenated | Yes |
|---|
| Suitability - Oil Resistance | Yes |
|---|
| Suitability - Outdoor | Yes |
|---|
| Suitability - Sunlight Resistance | Yes |
|---|
Flammability, LS0H, Toxicity Testing
| IEC Flammability | IEC 60332-1-2 |
|---|
| IEC 60754-1 - Halogen Amount | Zero |
|---|
| IEC 60754-2 - Halogen Acid Gas Amount - Max. Conductivity | 2.5 µS/mm |
|---|
| IEC 60754-2 - Halogen Acid Gas Amount - Min. pH | 4.3 |
|---|
| IEC 61034-2 - Smoke Density Min. Transmittance | 60% |
|---|
History
| Update and Revision | Revision Number: 0.33 Revision Date: 11-09-2022 |
|---|
Documentation
Product Bulletins
Catalogs
Solution Guides
Technical Resources
Data Sheets