Low Temp Rubber Lead Wire, 3/0AWG (630x26) Tinned Copper, CSPE Insulation, AWM 3193 CSA TYPE CL1052 600V 105C
Specifications
Specifications
Product Overview
Suitable Applications | Class 130(B) motor lead systems, internal wiring of appliances, oil resistance applications |
---|
Construction Details
Conductor
Element | Number of Element | Size | Stranding | Material |
---|
Conductor(s) | 1 | 3/0 AWG | 630x26 | TC - Tinned Copper |
Insulation
Material | Nom. Thickness | Nom. Insulation Diameter |
---|
CSPE - Chlorosulphonated Polyethylene | 0.098 in (2.5 mm) | 0.732 in (18.6 mm) |
Overall Cable Diameter (Nominal) | 0.732 in (18.6 mm) |
---|
Electrical Characteristics
Electricals
Nom. Conductor DCR | Max. Current |
---|
0.0724 Ohm/1000ft | 420.8 Amps per Conductor at 30ºC |
Voltage
UL Voltage Rating | Voltage Rating |
---|
600 V (AWM 3193) | 300 V (CSA CL-1052) |
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|
105°C | -30°C To +105°C |
Bend Radius
Stationary Min. | Installation Min. |
---|
7.32 in (186 mm) | 7.32 in (186 mm) |
Max. Pull Tension | 2178 lbs (987.9 kg) |
---|
Recommended Max Baking Cycles | 24 Hours @ 300°F (149°C) |
---|
Bulk Cable Weight | 661 lbs/1000ft |
---|
Standards and Compliance
Environmental Suitability | Indoor, Outdoor, Oil Resistance |
---|
Sustainability | CA Prop 65 |
---|
Flammability / Reaction to Fire | Horizontal flame |
---|
AWM Compliance | AWM 3193 |
---|
CEC / C(UL) Compliance | CL-1052 |
---|
European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
---|
APAC Compliance | China RoHS II (GB/T 26572-2011) |
---|
Product Notes
Notes | Exact strand count may vary. Separator material over conductor. |
---|
History
Update and Revision | Revision Number: 0.492 Revision Date: 01-20-2023 |
---|
Documentation
Catalogs
Tools
Compliance Documentation
Data Sheets