Rubber Lead Wire, 2/0AWG (504x26) Tinned Copper, EPDM Insulation, AWM 3499 7500V 150C
Specifications
Specifications
Product Overview
Suitable Applications | internal wiring of appliances, high voltage and high temperature applications |
---|
Construction Details
Conductor
Element | Number of Element | Size | Stranding | Material |
---|
Conductor(s) | 1 | 2/0 AWG | 504x26 | TC - Tinned Copper |
Insulation
Material | Nom. Thickness | Nom. Insulation Diameter |
---|
EPDM - Ethylene Propylene Diene Monomer | 0.134 in (3.40 mm) | 0.739 in (18.8 mm) |
Overall Cable Diameter (Nominal) | 0.739 in (18.8 mm) |
---|
Electrical Characteristics
Electricals
Nom. Conductor DCR | Max. Current |
---|
0.0913 Ohm/1000ft | 401.6 Amps per Conductor at 30ºC |
Voltage
UL Voltage Rating |
---|
7500 V (AWM 3499) |
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|
150°C | -55°C To +150°C |
Bend Radius
Stationary Min. | Installation Min. |
---|
7.39 in (188 mm) | 7.39 in (188 mm) |
Max. Pull Tension | 1606 lbs (728.5 kg) |
---|
Recommended Max Baking Cycles | 24 Hours @ 300°F (149°C) ~ 4 Hours @ 375°F (190°C) |
---|
Bulk Cable Weight | 562 lbs/1000ft |
---|
Standards and Compliance
Environmental Suitability | Indoor, Outdoor |
---|
Sustainability | CA Prop 65 |
---|
Flammability / Reaction to Fire | Horizontal flame |
---|
AWM Compliance | AWM 3499 |
---|
European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
---|
APAC Compliance | China RoHS II (GB/T 26572-2011) |
---|
Product Notes
Notes | Exact strand count may vary. |
---|
History
Update and Revision | Revision Number: 0.485 Revision Date: 01-20-2023 |
---|
Documentation
Catalogs
Tools
Compliance Documentation
Data Sheets