Security & Commercial Audio Cable, 2-18 AWG stranded bare copper conductors with Low Smoke Zero Halogen insulation, Beldfoil® shield, LSZH jacket with ripcord, CPR Cca
Specifications
Specifications
Product Overview
Suitable Applications | Intercom/PA Systems, Sound/Audio Systems,
Control Systems |
---|
Construction Details
Conductor
Size | Stranding | Material |
---|
18 | 7x26 | BC - Bare Copper |
Insulation
Material | Nom. Thickness | Nom. Insulation Diameter |
---|
LSZH - Low Smoke Zero Halogen (Flame Retardant) | 0.25 mm (0.0098 in) | 1.72 mm (0.0677 in) |
Outer Shield
Shield Type | Material | Coverage | Drainwire Type |
---|
Tape | Bi-Laminate (Alum+Poly) | 100% | 24 AWG (7x32) TC |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter | Ripcord |
---|
LSZH - Low Smoke Zero Halogen (Flame Retardant) | 1.0 mm (0.039 in) | 5.7 mm (0.22 in) | Yes |
Overall Cable Diameter (Nominal) | 5.70 mm (0.224 in) |
---|
Electrical Characteristics
Electricals
Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Nom. Capacitance Cond-to-Other (Conds + Shield) |
---|
21.3 Ohm/km (6.49 Ohm/1000ft) | 158 pF/m (48.2 pF/ft) | 295 pF/m (89.9 pF/ft) |
Mechanical Characteristics
Temperature
Installation | Storage |
---|
-20°C To +70°C | -30°C To +70°C |
Bend Radius
Installation Min. |
---|
57 mm (2.2 in) |
Max. Pull Tension | 90 N (20 lbf) |
---|
Standards and Compliance
Environmental Suitability | Indoor - Euroclass Cca, Non-Halogenated |
---|
Flammability / Reaction to Fire | IEC 60332-1-2 |
---|
CPR Compliance | CPR Euroclass: Cca-s1,d1,a1 |
---|
CENELEC Compliance | EN 50290-2-20 |
---|
European Halogen Free Standards | IEC 62821-1 Halogen Free Compliance = Yes, IEC 60754-2 - Halogen Acid Gas Amount - Max. Conductivity = 2.5 µS/mm, IEC 60754-2 - Halogen Acid Gas Amount - Min. pH = 4.3 |
---|
European Directive Compliance | EU Directive 2011/65/EU (RoHS 2) |
---|
History
Update and Revision | Revision Number: 0.3 Revision Date: 12-20-2022 |
---|
Documentation
Product Bulletins
Catalogs
Technical Resources
Data Sheets