Security & Commercial Audio Cable, 6-18 AWG stranded bare copper conductors with Low Smoke Zero Halogen insulation, LSZH jacket with ripcord, CPR Cca
Specifications
Specifications
Product Overview
| Suitable Applications | Intercom/PA Systems, Sound/Audio Systems,
Control Systems | 
|---|
Physical Characteristics (Overall)
Conductor
| AWG | Stranding | Material | Nominal Diameter | No. of Conductors | 
|---|
| 18 | 7x26 | BC - Bare Copper | 1.22 mm | 6 | 
Insulation
| Material | Nominal Diameter | Diameter +/- Tolerance | Nominal Wall Thickness | 
|---|
| LSZH - Low Smoke Zero Halogen (Flame Retardant) | 1.72 mm | 0.05 mm | 0.25 mm | 
Color Chart
| Color | 
|---|
| Black | 
| Red | 
| White | 
| Green | 
| Brown | 
| Blue | 
Outer Jacket
| Material | Nominal Diameter | Nominal Wall Thickness | 
|---|
| LSZH - Low Smoke Zero Halogen (Flame Retardant) | 7.3 mm | 1 mm | 
Electrical Characteristics
Conductor DCR
| Nominal Conductor DCR | 
|---|
| 21.3 Ohm/km | 
Capacitance
| Nom. Capacitance Conductor to Conductor | 
|---|
| 100 pF/m | 
Voltage
Temperature Range
| Installation Temperature Range | -20°C To +70°C | 
|---|
| Storage Temperature Range | -30°C To +70°C | 
|---|
Mechanical Characteristics
| Max. Pull Tension | 240 N | 
|---|
| Min. Bend Radius During Installation | 73 mm | 
|---|
| Min Setting Radius | 36 mm | 
|---|
Standards
| CPR Euroclass | Cca-s1,d1,a1 | 
|---|
Applicable Environmental and Other Programs
| Environmental Space | Indoor - Euroclass Cca | 
|---|
Flammability, LS0H, Toxicity Testing
| IEC Flammability | IEC 60332-1-2 | 
|---|
| IEC 60754-2 - Halogen Acid Gas Amount - Max. Conductivity | 2.5 µS/mm | 
|---|
| IEC 60754-2 - Halogen Acid Gas Amount - Min. pH | 4.3 | 
|---|
| IEC 61034-2 - Smoke Density Min. Transmittance | 60% | 
|---|
History
| Update and Revision | Revision Number: 0.13    Revision Date: 06-09-2023 | 
|---|