Security & Commercial Audio Cable, 3-10 AWG stranded bare copper conductors with Low Smoke Zero Halogen insulation, LSZH jacket with ripcord, CPR Cca
Specifications
Specifications
Product Overview
Suitable Applications | Intercom/PA Systems, Sound/Audio Systems,
Control Systems |
---|
Physical Characteristics (Overall)
Conductor
AWG | Stranding | Material | No. of Conductors |
---|
10 | 65x28 | BC - Bare Copper | 3 |
Insulation
Material | Nominal Diameter | Diameter +/- Tolerance | Nominal Wall Thickness |
---|
LSZH - Low Smoke Zero Halogen (Flame Retardant) | 4.0 mm | 0.05 mm | 0.2 mm |
Outer Jacket
Material | Nominal Diameter | Nominal Wall Thickness | Ripcord |
---|
LSZH - Low Smoke Zero Halogen (Flame Retardant) | 11.6 mm | 1.3 mm | Yes |
Table Notes | Ripcord provided under sheath |
---|
Electrical Characteristics
Conductor DCR
Nominal Conductor DCR |
---|
3.2 Ohm/km |
Capacitance
Nom. Capacitance Conductor to Conductor |
---|
100 pF/m |
Voltage
Temperature Range
Installation Temperature Range | -20°C To +70°C |
---|
Storage Temperature Range | -30°C To +70°C |
---|
Mechanical Characteristics
Max. Pull Tension | 450 N |
---|
Min. Bend Radius During Installation | 116 mm |
---|
Min Setting Radius | 58 mm |
---|
Standards
CPR Euroclass | Cca-s1,d1,a1 |
---|
Applicable Environmental and Other Programs
Environmental Space | Indoor - Euroclass Cca |
---|
Flammability, LS0H, Toxicity Testing
IEC Flammability | IEC 60332-1-2 |
---|
IEC 60754-2 - Halogen Acid Gas Amount - Max. Conductivity | 2.5 µS/mm |
---|
IEC 60754-2 - Halogen Acid Gas Amount - Min. pH | 4.3 |
---|
IEC 61034-2 - Smoke Density Min. Transmittance | 60% |
---|
History
Update and Revision | Revision Number: 0.13 Revision Date: 12-20-2022 |
---|
Documentation
Product Bulletins
Catalogs
Technical Resources
Data Sheets