Fire Alarm Cable, Riser-FPLR, 2-14 AWG solid bare copper conductors with polypropylene insulation, overall Beldfoil® shield, PVC jacket with ripcord
Specifications
Specifications
Product Overview
| Suitable Applications | Fire Alarm, Monitor/Detection, Circuits: Audio, Control, Initiating, Notification, Noisy Environment |
|---|
Construction Details
Conductor
| Element | Number of Element | Size | Stranding | Material |
|---|
| Conductor(s) | 2 | 14 AWG | Solid | BC - Bare Copper |
Insulation
| Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
|---|
| Conductor(s) | PP - Polypropylene | 0.010 in (0.25 mm) | 0.845 in (21.5 mm) | Black, Red |
Outer Shield
| Shield Type | Material | Coverage | Drainwire Type |
|---|
| Tape | Bi-Laminate (Alum+Poly) | 100% | 22 AWG (Solid) TC |
Outer Jacket
| Material | Nom. Thickness | Nom. Diameter | Ripcord |
|---|
| PVC - Polyvinyl Chloride | 0.017 in (0.43 mm) | 0.209 in (5.31 mm) | Yes |
| Overall Cable Diameter (Nominal) | 0.209 in (5.31 mm) |
|---|
Electrical Characteristics
Electricals
| Element | Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Nom. Capacitance Cond-to-Other (Conds + Shield) | Max. Current |
|---|
| Conductor(s) | 2.43 Ohm/1000ft | 60 pF/ft (200 pF/m) | 108 pF/ft (354 pF/m) | 25 Amps per conductor @ 30°C |
Voltage
| UL Voltage Rating |
|---|
| 300 V (FPLR) |
Mechanical Characteristics
Temperature
| UL Temperature | Operating |
|---|
| 75°C | -20°C to +75°C |
Bend Radius
| Stationary Min. | Installation Min. |
|---|
| 3.075 in (78.11 mm) | 3.075 in (78.11 mm) |
| Max. Pull Tension | 206.6 lbs (93.71 kg) |
|---|
| Bulk Cable Weight | 36 lbs/1000ft |
|---|
Standards and Compliance
| Environmental Suitability | Indoor - Riser, Indoor |
|---|
| Flammability / Reaction to Fire | UL 1666 Riser, IEEE 1202 FT4, IEC 60332-1-2 |
|---|
| CPR Compliance | CPR Euroclass: Eca |
|---|
| NEC / UL Compliance | Article 760, FPLR |
|---|
| European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
|---|
| UK Regulation Compliance | UKCA Mark |
|---|
| APAC Compliance | China RoHS II (GB/T 26572-2011) |
|---|
| Other Standard Compliance(s) | California State Fire Marshall |
|---|
| Plenum Number | 6120FL |
|---|
History
| Update and Revision | Revision Number: 0.447 Revision Date: 01-20-2023 |
|---|
Documentation
Product Bulletins
Compliance Documentation
Data Sheets