Security & Sound Cable, Rated-CMG-FPL-PLTC, 4-18 AWG stranded tinned copper conductors with PVC insulation, waterblocking tape, Beldfoil® shield and PVC jacket
Specifications
Specifications
Product Overview
Suitable Applications | Security System, Intercom/PA, Audio/Speaker, Power-Limited Controls, Noisy & Wet Location, Below-Grade Duct |
---|
Construction Details
Conductor
Element | Number of Element | Size | Stranding | Material |
---|
Conductor(s) | 4 | 18 AWG | 7x26 | TC - Tinned Copper |
Insulation
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|
Conductor(s) | PVC - Polyvinyl Chloride | 0.010 in (0.25 mm) | 0.066 in (1.7 mm) | Black, White, Red, Green |
Outer Shield
Shield Type | Material | Coverage | Drainwire Type |
---|
Tape | Bi-Laminate (Alum+Poly) | 100% | 20 AWG (7x28) TC |
Waterblocking | Waterblock Tape |
---|
Outer Jacket
Material | Nom. Thickness | Nom. Diameter |
---|
PVC - Polyvinyl Chloride | 0.037 in (0.94 mm) | 0.259 in (6.58 mm) |
Overall Cable Diameter (Nominal) | 0.259 in (6.58 mm) |
---|
Electrical Characteristics
Electricals
Element | Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond |
---|
Conductor(s) | 6.6 Ohm/1000ft | 40 pF/ft (130 pF/m) |
Voltage
UL Voltage Rating |
---|
300 V (CMG, FPL, PLTC-ER) |
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|
105°C | -30°C to +105°C |
Bend Radius
Stationary Min. | Installation Min. |
---|
2.6 in (66 mm) | 2.6 in (66 mm) |
Max. Pull Tension | 102 lbs (46.3 kg) |
---|
Bulk Cable Weight | 45 lbs/1000ft |
---|
Standards and Compliance
Environmental Suitability | Water Exposure/Below-Grade Conduit, Indoor, Outdoor, Sunlight Resistance, Burial |
---|
Flammability / Reaction to Fire | UL 1685 FT4 Loading, FT4, IEEE 1202 |
---|
CPR Compliance | CPR Euroclass: Eca |
---|
NEC / UL Compliance | Article 725, Article 760, Article 800, CMG, FPL, PLTC |
---|
CEC / C(UL) Compliance | CMG |
---|
European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
---|
UK Regulation Compliance | UKCA Mark |
---|
APAC Compliance | China RoHS II (GB/T 26572-2011) |
---|
History
Update and Revision | Revision Number: 0.458 Revision Date: 04-14-2023 |
---|
Documentation
Product Bulletins
Solutions Guide
Tools
Compliance Documentation
Data Sheets