Description

Fire Alarm Cable, Riser-FPLR, 8-18 AWG solid bare copper conductors with polypropylene insulation, PVC jacket with ripcord

Specifications

Specifications

Product Overview

Suitable ApplicationsFire Alarm, Monitor/Detection, Circuits: Audio, Control, Initiating, Notification

Construction Details

Conductor

ElementNumber of ElementSizeStrandingMaterial
Conductor(s)818 AWGSolidBC - Bare Copper

Insulation

ElementMaterialNom. ThicknessNom. Insulation DiameterColor Code
Conductor(s)PP - Polypropylene0.007 in (0.18 mm)0.055 in (1.4 mm)Black, Red, Brown, Blue, Orange, Yellow, Purple, Green

Outer Shield

Material
No Shield

Outer Jacket

MaterialNom. ThicknessNom. DiameterRipcord
PVC - Polyvinyl Chloride0.018 in (0.46 mm)0.216 inYes
Overall Cable Diameter (Nominal)0.216 in

Electrical Characteristics

Electricals

ElementNom. Conductor DCRNom. Capacitance Cond-to-CondMax. Current
Conductor(s)6.4 Ohm/1000ft22 pF/ft (72 pF/m)3.5 Amps per Conductor at 25ºC

Voltage

UL Voltage Rating
300 V

Mechanical Characteristics

Temperature

UL TemperatureOperating
75°C-20°C To +75°C

Bend Radius

Stationary Min.Installation Min.
1.72 in (43.7 mm)1.72 in
Max. Pull Tension156.8 lbs (71.12 kg)
Bulk Cable Weight50 lbs/1000ft

Standards and Compliance

Environmental SuitabilityIndoor
Flammability / Reaction to FireUL1666 Riser
NEC / UL ComplianceArticle 760, FPLR
European Directive ComplianceEU CE Mark, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)
Other Standard Compliance(s)California State Fire Marshall
Plenum Number6326UL