Fire Alarm Cable, Riser-FPLR, 2-22 AWG solid bare copper conductors with PVC insulation, PVC jacket with ripcord
Specifications
Specifications
Product Overview
Suitable Applications | Fire Alarm, Monitor/Detection, Circuits: Audio, Control, Initiating, Notification |
---|
Construction Details
Conductor
Element | Number of Element | Size | Stranding | Material |
---|
Pair(s) | 1 | 22 AWG | Solid | BC - Bare Copper |
Insulation
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|
Pair(s) | PO - Polyolefin | 0.007 in (0.18 mm) | 0.040 in (1.0 mm) | Black and Red |
Outer Shield
Outer Jacket
Material | Nom. Thickness | Nom. Diameter | Ripcord |
---|
PVC - Polyvinyl Chloride | 0.017 in (0.43 mm) | 0.114 in | Yes |
Overall Cable Diameter (Nominal) | 0.114 in |
---|
Electrical Characteristics
Electricals
Element | Nom. Conductor DCR | Max. Current |
---|
Pair(s) | 18.4 Ohm/1000ft | 2.8 Amps per Conductor at 25ºC |
Voltage
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|
75°C | -20°C To +75°C |
Bend Radius
Stationary Min. | Installation Min. |
---|
0.91 in (23 mm) | 0.91 in |
Max. Pull Tension | 15.6 lbs (7.08 kg) |
---|
Bulk Cable Weight | 8 lbs/1000ft |
---|
Standards and Compliance
Environmental Suitability | Indoor |
---|
Flammability / Reaction to Fire | UL1666 Riser, FT4 |
---|
NEC / UL Compliance | Article 760, FPLR |
---|
History
Update and Revision | Revision Number: 0.130 Revision Date: 05-05-2023 |
---|
Documentation
Product Bulletins
Data Sheets