Security & Sound Cable , Plenum-FPLP, 2-12 AWG stranded bare copper conductors with Flamarrest® insulation, and Flamarrest® jacket with ripcord
Specifications
Specifications
Product Overview
Suitable Applications | Fire Alarm, Monitor/Detection, Circuits: Audio, Control, Initiating, Notification |
---|
Construction Details
Conductor
Element | Number of Element | Size | Stranding | Material |
---|
Conductor(s) | 2 | 12 | 19x25 | BC - Bare Copper |
Insulation
Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|
PVC - Polyvinyl Chloride | 0.011 in (0.28 mm) | 0.057 in (1.4 mm) | Black, Red |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter | Ripcord |
---|
PVC - Polyvinyl Chloride | 0.015 in (0.38 mm) | 0.256 in | Yes |
Electrical Characteristics
Electricals
Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Max. Current |
---|
1.68 Ohm/1000ft | 34.75 pF/ft (114.0 pF/m) | 30 Amps per Conductor at 25ºC |
Voltage
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|
75°C | 0°C To +75°C |
Bend Radius
Stationary Min. | Installation Min. |
---|
2.04 in (51.8 mm) | 2.04 in |
Max. Pull Tension | 152 lbs (68.9 kg) |
---|
Bulk Cable Weight | 52 lbs/1000ft |
---|
Standards and Compliance
Environmental Suitability | Indoor |
---|
Flammability / Reaction to Fire | NFPA 262 (UL910) |
---|
NEC / UL Compliance | Article 760, FPLP |
---|
European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
---|
APAC Compliance | China RoHS II (GB/T 26572-2011) |
---|
Non-Plenum Number | 5000UL |
---|
History
Update and Revision | Revision Number: 0.141 Revision Date: 05-05-2023 |
---|
Documentation
Product Bulletins
Compliance Documentation