Teck90 1000V, 4+G Conductor 2/0+6AWG (19x11H) Bare Copper, XLPE Insulation M4 Color Code, PVC Inner Jacket, Aluminum Interlock Armor, Black PVC Outer Jacket, CSA HL SUN RES -40C
Specifications
Specifications
Product Overview
Suitable Applications | Power and Control Applications up to 600V |
---|
Construction Details
Conductor
Element | Number of Element | Size | Stranding | Material |
---|
Conductor(s) | 4 | 2/0 AWG | 19x11 | BC - Bare Copper |
Ground Wire | 1 | 6 AWG | 7x14 | BC - Bare Copper |
Insulation
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|
Conductor(s) | XLP, XLPO, XLPE (Thermoset) | 0.081 in (2.1 mm) | 0.571 in mm | Black, Red, White, Blue |
Ground Wire | No Insulation | | | |
Outer Shield
Inner Jacket
Material | Nom. Thickness | Nom. Diameter |
---|
PVC - Polyvinyl Chloride | 0.083 in (2.1 mm) | 1.542 in (39.17 mm) |
Armor
Armor Type & Material | Diameter Over Armor |
---|
AIA - Aluminum Interlock Armor | 1.822 in (46.28 mm) |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter | Ripcord |
---|
PVC - Polyvinyl Chloride | 0.053 in (1.3 mm) | 1.928 in | Yes |
Overall Cable Diameter (Nominal) | 1.928 in |
---|
Electrical Characteristics
Electricals
Element | Nom. Conductor DCR | Max. Current |
---|
Conductor(s) | 0.0827 Ohm/1000ft | 136 Amps per Conductor at 30ºC |
Ground Wire | 0.419 Ohm/1000ft (1.37 Ohm/km) | |
Voltage
Voltage Rating |
---|
1000 V (TECK 90) |
Mechanical Characteristics
Temperature
Operating | Installation |
---|
-40°C To +90°C | -25°C To +90°C |
Bend Radius
Stationary Min. | Installation Min. |
---|
15.42 in (391.7 mm) | 15.42 in |
Max. Pull Tension | 7044.7 lbs (3195.4 kg) |
---|
Bulk Cable Weight | 2693 lbs/1000ft |
---|
Standards and Compliance
Environmental Suitability | Indoor, Outdoor, Sunlight Resistance, UV Resistance, Burial |
---|
Sustainability | CA Prop 65 |
---|
CEC / C(UL) Compliance | TECK 90, HL |
---|
European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
---|
APAC Compliance | China RoHS II (GB/T 26572-2011) |
---|
History
Update and Revision | Revision Number: 0.254 Revision Date: 05-05-2023 |
---|
Documentation
Catalogs
Technical Resources
Videos
Compliance Documentation
Data Sheets